SiUS121736EA Troubleshooting for Outdoor Unit
Service Diagnosis 184
7.4 Unspecified Voltage (Between Indoor Unit and Outdoor
Unit), Anti-Icing Control in Other Rooms
Error Code UA, UH
Outdoor Unit LED
Display
A j 1 h 2 h 3 h 4 h 5 h
Method of Error
Detection
A wrong connection is detected by checking the combination of indoor and outdoor units on the
microcomputer.
Error Decision
Conditions
Anti-icing control in other rooms
Unspecified internal and/or external voltages
Mismatching of indoor and outdoor units
Supposed
Causes
Anti-icing function in other rooms
Power supply voltage out of specification
Wrong models interconnected
Wrong indoor unit PCB or outdoor unit PCB mounted
Troubleshooting
Note: Refer to Anti-icing control for indoor unit on page 185 for details.
(R21922)
Caution
NO
YES
NO
YES
NO
YES
Check the model combination.
Error displayed while
operating?
Power
supply voltage as
specified?
Matched compatibly?
The anti-icing function is
activated in other rooms.
Refer to A5.
Correct the power supply
voltage.
Match the compatible models.
Check the combination of all
connected models.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.

Table of Contents

Other manuals for Daikin 4MXS36RMVJUA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin 4MXS36RMVJUA and is the answer not in the manual?

Daikin 4MXS36RMVJUA Specifications

General IconGeneral
BrandDaikin
Model4MXS36RMVJUA
CategoryAir Conditioner
LanguageEnglish

Related product manuals