EasyManuals Logo
Home>Daikin>Air Conditioner>E Series

Daikin E Series User Manual

Daikin E Series
453 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #103 background imageLoading...
Page #103 background image
Protection Control SiAU18-715
90 Function
4.2 Low Pressure Protection Control
This low pressure protection control is used to protect compressors against the transient
decrease of low pressure.
[In cooling operation]
[In heating operation]
Pe<0.25MPa
36Hz Unload
Pe>0.39MPa
Pe
<
0.07MPa
Low pressure not limited
Low pressure
standby
Low pressure
limited
Pe: LP pressure sensor detection
value
When occurring 3 times within 30 min.,
the malfunction code "E4"
is output.
Pe<0.15MPa Pe>0.30MPa
Hot gas SVP = OFF
Hot gas SVP = ON
&
• Ts-Teg
<
8deg
• Pe
>
0.06MPa
• Pe
>
0.09MPa
or
After 10 sec.Pe
<
0.17MPa
Pe
<
0.17MPa
Pe
>
0.20MPa
Pe< 0.07MPa
Current step limited
After 15 sec.
Low pressure not limited
Low pressure limited
INV upper limit frequency :
1-step up from current
compressor frequency
Pe: LP pressure sensor detection
value
INV upper limit frequency :
3-step down from current
compressor frequency
When occurring 3 times within 30 min.,
the malfunction code "E4"
is output.
Low pressure
standby
Pe<0.12MPa Pe>0.17MPa
Hot gas SVP = OFF
Hot gas SVP = ON

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin E Series and is the answer not in the manual?

Daikin E Series Specifications

General IconGeneral
BrandDaikin
ModelE Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals