Specifications SiAU18-715
14 Specifications
1. Specifications
1.1 Cooling Only
1.1.1 Outdoor Units
50Hz 220-230-240V
Note:
1.
Refrigerant charge is required. (Chargeless piping length 0m)
Formula for calculation charge : R (kg)
R = Total length (m) of liquid pipe size at
φ
9.5×0.054 +Total length (m) of liquid piping size at
φ
6.4×0.022
2. The data are based on the conditions shown in the table below.
Model RMKS112EV1A RMKS140EV1A RMKS160EV1A
4HP 5HP 6HP
Cooling Capacity
kW
(kcal/h)
11.2 (9,630) 14.0 (12,040) 15.5 (13,330)
Total Indoor Unit Capacity kW 5.5~14.5 7.0~18.2 8.0~20.8
Power Consumption W
Running Current A
Casing Color Ivory White
Compressor
Type Hermetically Sealed Scroll Type
Model JT100FCVD
Motor Output
(2.2kW/60rps)
kW 2.5 3.0 3.5
Refrigerant
Oil
Model DAPHNE FVC68D
Charge L 1.5
Refrigerant
Type R-410A
Charge kg 4.0
Air Flow Rate
(H)
m³/min (cfm) 106 (3742)
Fan
Type Propeller
Motor Output W 70+70
Running Current A 0.4+0.4
Power Consumption W 88+88
Starting Current A 15.3-14.5-14.3 21.1-20.1-19.8 24.2-23.9-23.6
Dimensions (H×W×D) mm 1,345×900×320
Package Dimensions (H×W×D) mm 1,475×925×390
Weight kg 125
Gross Weight kg 146
Operation Sound dBA 52 53 54
Piping
Connection
Liquid mm
φ
9.5 (Flare Connection)
Gas mm
φ
19.1 (Brazing Connection)
Drain mm
φ
18
Heat Insulation Both Liquid and Gas Pipes
No. of Wiring Connection 3 For Power Supply (Including Earth Wiring), 2 For Interunit Wiring (Outdoor Unit-BP)
Total piping
length
O.U. - BP m 55
BP - I.U. m 60 80 90
System Total m 115 135 145
Max. piping
length
BP - I.U. m 15
1st Branch - I.U. m 40
Max. level
difference
O.U. - BP m 30
O.U. - I.U. m 30
BP - BP, I.U. - I.U. m 15
Necessity of Additional Charge
kg/m Necessary
Cooling Piping Length
Indoor ; 27°CDB / 19°CWB
Outdoor ; 35°CDB
Main Piping : 5m
Branch Piping : 3m
Level difference : 0m
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
BP Unit
Outdoor Unit
Main Piping
Branch Piping
Indoor Unit
(Q0143)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin E Series and is the answer not in the manual?

Daikin E Series Specifications

General IconGeneral
BrandDaikin
ModelE Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals