Protection Control SiAU18-715
92 Function
4.4 Inverter Protection Control
Inverter current protection control and inverter fin temperature control are performed to prevent
tripping due to a malfunction, or transient inverter overcurrent, and fin temperature increase.
[Inverter overcurrent protection control]
[Inverter fin temperature control]
Not limited
Limited
Inverter current >23.8A
Inverter current
Inverter current 24.9A continues for 260 sec.
>23.8A
Inverter current 23.8A
INV upper limit frequency=max Hz
&
10 sec.
Matching of frequency
&
When occurring 4 times within 60 min.,
the malfunction code "L8 " is output.
INV upper limit frequency:
1-step down from current
compressor frequency
INV upper limit frequency:
1-step up from current
compressor frequency
Inverter current
standby
Inverter current 23.8A
continues for 3 min.
Status quo
Without conditions
Not limited
Limited
Tfin78˚C
Tfin78˚C
Tfin83˚C
Fin temp. standby
Tfin<75 ˚C
INV upper limit frequency=max Hz
&
When occurring 4 times within 60 min.,
the malfunction code "L4" is output.
INV upper limit frequency:
1-step down from current
compressor frequency
10 sec.
Macthing of frequency
&
Tfin75˚C
continues for 3 min.
INV upper limit frequency:
1-step up from current
compressor frequency
Status quo
Without conditions