SiAU18-715 Basic Control
Function 79
D Control Receiving the capacity request signal from the indoor unit, the outdoor unit corrects its target
pressure for capacity control.
Controls
D signal from indoor unit as follows.
UP control : When the UP command come from more than one indoor unit among
thermostat-ON indoor units.
Down control : When the down command come from all indoor units among thermostat-ON
indoor units.
Keep control : Except for the above
About detail of
D signal, refer to P96
Cooling Operation
TeS = TeS initial value + KTe2
KTe2 : Correction value by
D signal in cooling.
KTe2 = 0
(without correction)
D control
Keep the current KTe2
KTe2 = KTe2 0.5 KTe2 = KTe2 + 0.5
Up control by D signal
continues 120 sec.
Down control by D signal
continues 120 sec.
During compressor frequency PI
control (KTe2 = 0)
Not during compressor frequency PI
control
(Q0396)