ESIE15-11A | Part 3. Field settings 8. Selfcleaning panel BYCQ140D7G
23/09/16 Page 47
VRV4 indoor units
8. Selfcleaning panel BYCQ140D7G
DIP-switches on PCB
14/
24
2 when to display cleaning requirement on the
remote control according to number of operating
hours
01 Display after 1.250h
02 Display after 2.500h
03 Display after 5.000h
3 Display filter change on the remote control
according to number of operating hours
01 no display
02 Display after 32.000h
03 Display after 48.000h
04 Display after 72.000h
4 Panel indicator (green) 01 On while in a/c operation and filter cleaning operation
02 possible to turn on while in filter cleaning operation only
03 off while in a/c operation and filter cleaning operation
04 On
8 auto cleaning program 01 choice between auto and schedule
02 only schedule (auto not in menu)
9 Dust amount setting 01 standard
02 dust amount big
BS1 Cleaning test
Push for 1 second to start the cleaning test
BS2 Error reset
Push for 1 second to reset an error
DIP DS1 – 1 Self-cleaning available / unavailable
ON - not available
OFF - available
DIP DS1 – 2 Light intensity of the infrared sensor
ON - high
OFF - normal