Points of Analysis Si30-408
182 Service Checker Type3 Application Edition
5.5 Method of Mounting Sensor Kit
1. Determine the position to mount thermistor.
2. Clean the pipe. (Wipe condensate or dirt off the pipe, if any.)
Caution Be sure to stop equipment before mounting the thermistor to a low temperature pipe.
(If the pipe is condensed or frozen, no accurate measurements are enabled.)
3. Bring the thermistor into close contact with the pipe in parallel and tightly wind aluminum
tape around them.
4. Wrap anti-sweat insulation tube or the like around pipe and thermistor (in order to make
them insensitive to ambient temperature.
5. Tie both ends of the anti-sweat vessel.