EasyManuals Logo

Daikin RX10MY1 User Manual

Daikin RX10MY1
255 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #37 background imageLoading...
Page #37 background image
Si30-408 Control of Indoor Unit
Basic Information 33
4.5 Thermostat Control in Cooling / Heating Automatic
Operation
In cooling / heating automatic operation, the unit is controlled as shown below based on set
"differential value". Factory setting of differential valve is 5°C. As to charging method of setting
value, refer to page 43 and page 44.
Cooling/Heating
Differential: at
5°C
Automatic heating
22˚C
Automatic cooling
27˚C
Display selection
CoolingHeating
Display selection
HeatingCooling
Cooling thermostat ON
Cooling thermostat OFF
3˚C
Heating thermostat OFF
Heating thermostat ON
T=5˚C
T/2+2˚C(4.5˚C)
Cooling / heating differential : at 3˚C
Automatic heating
22˚C
Automatic cooling
25˚C
T=3˚C

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin RX10MY1 and is the answer not in the manual?

Daikin RX10MY1 Specifications

General IconGeneral
BrandDaikin
ModelRX10MY1
CategoryInverter
LanguageEnglish

Related product manuals