14 | P a g e
Unit shut down
Shut down procedure
Steps
Description
1
Shut down - Circuit
1.1
To shutdown circuit 1# or circuit 2#, turn the switch of the corresponding circuit to “OFF”.
After these operations, the circuit will shut down automatically.
2
Shut down - Unit
2.1
Turn Q1(1#SYS SW.) and Q2(2#SYS SW.) to OFF
2.2
Turn Q0 (UNIT SWITCH) to OFF. After these operations, the unit will shut down
automatically.
5.2 Parameter Viewing and setting
After entering the user password, you can view and modify parameters at the user level. The
default user password is 1990. Parameter setting must be in accord with this operation manual.
Improper setting can cause erratic chiller operation and damage to the chiller.