32 | P a g e
6. UNIT PARAMETERS
6.1 Unit Setpoints
Menu
Factory Default
Setting
Range
Unit
Authorisation
Minimum
Maximum
R*
W*
1.View/Set ACSys(Master)
1.1.Status/Settings
ACSys Enable
Enable
Disable
Enable
--
U*
U
Control Source
Local
Local
Network
--
U
S
1.2.Set-Up
Start Up DT
2.7
0.0
5.0
dK
U
S
C Shut Dn DT
1.5
0.0
1.7
dK
U
S
H Shut Dn DT
2.5
0.0
2.7
dK
U
S
Stg Up DT
0.5
0.0
1.7
dK
U
S
Stg Dn DT
0.7
0.0
1.7
dK
U
S
Max Pulldn
2.5
0.5
2.5
℃/min
U
S
Stg Up Delay
5.0
0.0
60.0
min
U
S
Stg Dn Delay
3.0
3.0
30.0
min
U
S
Lt Ld Stg Dn %
40.0
25.0
50.0
%
S
S
Hi Ld Stg Up %
80.0
50.0
100.0
%
S
S
M Sequence
1
1
2
--
S
S
S Sequence
1
1
2
--
S
S
Auto Restart
Yes
No
Yes
--
S
S
1.3.Temperatures
Heat LWT 1
45.0
25.0
55.0
U
U
Heat LWT 2
45.0
25.0
55.0
U
U
Cool LWT 1
7.0
4.0
15.0
U
U
Cool LWT 2
7.0
4.0
15.0
U
U
Ice LWT
-4.0
-8.0
4.0
U
U
1.4.Power Conservation
Setpoint Reset
None
None
4-20mA
ReturnOat
--
U
U
Max Reset
5.0
0.0
10.0
dK
U
U
Start Reset DT
5.0
0.0
10.0
dK
U
U
Max Reset OAT
15.5
10.0
29.4
U
U
Strt Reset OAT
23.8
10.0
29.4
U
U
1.5.Calibrate Sensors
HP1 LWT Offset
0.0
-2.8
2.8
dK
S
S
HP2 LWT Offset
0.0
-2.8
2.8
dK
S
S
3.View/Set Unit
3.1.Unit Status/Settings
Chiller Enable
Enable
Disable
Enable
--
U*
U
Control Source
Local
Local
Network
--
U
S
Clr Stg Delays
Off
Off
On
--
S*
S
Clr Ice Dly
Off
Off
On
--
S
S