EasyManuals Logo

Daikin VRV Series User Manual

Daikin VRV Series
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #19 background imageLoading...
Page #19 background image
17
11.4 Malfunction codes
Incaseamalfunctioncodeappearsontheindoor
unituserinterfacedisplay,contactyourinstaller
andinformthemalfunctioncode,theunittype,and
serialnumber(youcanndthisinformationonthe
nameplateoftheunit).
Foryourreference,alistwithmalfunctioncodesis
provided.Yo u can,dependingonthelevelofthe
malfunctioncode,resetthecodebypushingthe
ON/OFFbutton.Ifnot,askyourinstallerforadvice.
Malfunction
code
Contents
Main code
A0
Externalprotectiondevicewasactivated
a1
EEPROMfailure(indoor)
A3
Drainsystemmalfunction(indoor)
A6
Fanmotormalfunction(indoor)
A7
Swingapmotormalfunction(indoor)
A9
Expansionvalvemalfunction(indoor)
AF
Drainmalfunction(indoorunit)
Ah
Filterdustchambermalfunction(indoor)
AJ
Capacitysettingmalfunction(indoor)
C1
TransmissionmalfunctionbetweenmainPCBand
subPCB(indoor)
C4
Heatexchangerthermistormalfunction
(indoor;liquid)
C5
Heatexchangerthermistormalfunction
(indoor;gas)
C9
Suctionairthermistormalfunction(indoor)
CA
Dischargeairthermistormalfunction(indoor)
CE
Movementdetectororoortemperaturesensor
malfunction(indoor)
CJ
Userinterfacethermistormalfunction(indoor)
e1
PCBmalfunction(outdoor)
e3
Highpressureswitchwasactivated
e4
Lowpressuremalfunction(outdoor)
e5
Compressorlockdetection(outdoor)
e6
Compressordamagealarm
e7
Fanmotormalfunction(outdoor)
e9
Electronicexpansionvalvemalfunction(outdoor)
F3
Dischargetemperatureoroverloadprotectorwas
activated(outdoor)
f4
Abnormalsuctiontemperature(outdoor)
f6
Refrigerantoverchargedetection
H3
Highpressureswitchwasactivated
H5
Overloadprotectormalfunction
H7
Fanmotortrouble(outdoor)
H9
Ambienttemperaturesensormalfunction(outdoor)
J1
Pressuresensormalfunction
J3
Dischargetemperaturesensormalfunction(outdoor)
J5
Suctiontemperaturesensormalfunction(outdoor)
J6
De-icingtemperaturesensormalfunction(outdoor)
J7
Liquidtemperaturesensor(aftersubcoolHE)
malfunction(outdoor)
J8
Liquidtemperaturesensor(coil)malfunction(outdoor)
Malfunction
code
Contents
Main code
J9
Gastemperaturesensor(aftersubcoolHE)
malfunction(outdoor)
JA
Highpressuresensormalfunction(S1NPH)
JC
Lowpressuresensormalfunction(S1NPL)
L1
INVcircuitabnormal
L4
Fintemperatureabnormal
L5
INVcircuitfaulty
L8
Compressorovercurrentdetected
L9
INVcompressorstartupabnormal
Lc
INVcircuittransmissiontrouble
P1
INVunbalancedpowersupplyvoltage
p2
Autochargeoperationrelated
P4
Finthermistormalfunction
p8
Autochargeoperationrelated
p9
Autochargeoperationrelated
pj
Capacitysettingmalfunction(outdoor)
u0
Refrigerantshortagewarning
u2
INVvoltagepowershortage
u3
Systemtestrunnotyetexecuted
u4
Faultywiringindoor/outdoor
u5
Abnormaluserinterface-indoorcommunication
u8
Abnormalmain-subuserinterfacecommunication
u9
Systemmismatch.Wrongtypeofindoorunitscombined.
Indoorunitmalfunction.
ua
Connectionmalfunctionoverindoorunitsortype
mismatch
uc
Centralizedaddressduplication
ue
Malfunctionincommunicationcentralizedcontrol
device-indoorunit
uf
Autoaddressmalfunction(inconsistency)
uh
Autoaddressmalfunction(inconsistency)
01_EN_3P344160-11V.indd 17 08-Oct-20 9:22:57 AM

Table of Contents

Other manuals for Daikin VRV Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin VRV Series and is the answer not in the manual?

Daikin VRV Series Specifications

General IconGeneral
TypeVariable Refrigerant Volume (VRV)
Energy EfficiencyHigh
RefrigerantR410A or R32
Inverter TechnologyYes
ControlCentralized
ApplicationResidential, Commercial
Indoor Unit TypesCeiling Cassette, Ceiling Suspended, Wall Mounted, Floor Standing, Concealed Duct
Outdoor Unit OptionsMultiple Units
Noise Level (Indoor Unit)19 dB(A) to 45 dB(A)

Related product manuals