© Danfoss A/S (AC-MCI/MWA), 2012-05 DKRCI.PD.SC0.C3.02 / 520H5687 13
Liquid Level Sensor, AKS 4100/4100U
Connect the device to the power supply
(see the product instruction for detail on
electrical installation/connection).
Press 3 times.
Press
Press
or
to select between SINGLE
or COAXIAL. Choose COAXIAL and
press to conrm.
Press (YES) to conrm
Press to change GAS EPS.R.
(Select the correct value from the tables
on page 16)
Press to change cursor-
position.
Press
to decrease the value or
to
increase the value.
AKS 4100
QUICK SETUP ?
YES NO
AKS 4100
PROBE TYPE
SINGLE CABLE
Press to conrm.
Press
to change the PROBE LENGTH.
Press
to change the position of the
cursor.
Press
to decrease the value or
to
increase the value.
Press to conrm.
Press
to change of SCALE 4 mA.
Press
to change the cursor position.
Press
to decrease the value or
to
increase the value.
Press to conrm.
Press
to change of SCALE 20 mA.
Press
to change the cursor position.
Press
to decrease the value or
to
increase the value.
Press to conrm.
Wait for QUICK SETUP to complete.
Count down from 8 sec.
Press to conrm.
Press
or
to select between
STORE NO or STORE YES.
Press to conrm.
Default screen appears:
Quick Setup completed
You have the possibility of checking your
settings by pressing
twice.
Press to return to default screen.
Quick Setup (all values below are only examples)
Connect the device to the power supply
Press 3 times.
Press
Press
or
to select between SINGLE
or COAXIAL. Choose COAXIAL and
press to conrm.
Press
(NO) to conrm
AKS 4100
QUICK SETUP ?
YES NO
AKS 4100
PROBE TYPE
SINGLE CABLE
Press
to change the PROBE LENGTH.
Press
to change the position of the
cursor.
Press
to decrease the value or
to
increase the value.
Press to conrm.
Press
to change of SCALE 4 mA.
Press
to change the cursor position.
Press
to decrease the value or
to
increase the value.
Press to conrm.
Press
to change of SCALE 20 mA.
Press
to change the cursor position.
Press
to decrease the value or
to
increase the value.
Press to conrm.
Wait for QUICK SETUP to complete.
Count down from 8 sec.
Press to conrm.
Press
or
to select between
STORE NO or STORE YES.
Press to conrm.
Default screen appears:
Quick Setup completed
AKS 4100
GAS EPS R ?
001.000
AKS 4100
PROBE LENGTH
05000 mm
AKS 4100
SCALE 4 mA
04946 mm
AKS 4100
SCALE 20 mA
00070 mm
AKS 4100
QUICK SETUP
COMPLETED IN 8
AKS 4100
1.0.0
QUICK START
AKS 4100
1.0.0
STORE NO
AKS 4100
DISTANCE
5000 mm
When CO
2
is used:
For all other refrigerants:
AKS 4100
LIQUID CO2 ?
YES NO
AKS 4100
LIQUID CO2 ?
YES NO
AKS 4100
SCALE 4 mA
04946 mm
AKS 4100
SCALE 20 mA
00070 mm
AKS 4100
QUICK SETUP
COMPLETED IN 8
AKS 4100
1.0.0
STORE NO
AKS 4100
DISTANCE
5000 mm
AKS 4100
1.0.0
QUICK START
AKS 4100
PROBE LENGTH
05000 mm
COAXIAL version
AKS 4100
QUICK SETUP ?
YES NO
AKS 4100
QUICK SETUP ?
YES NO
AKS 4100
COAXIAL 2200 mm
(0 %) 4 mA 1900 mm
(100 %) 20 mA 70 mm

Other manuals for Danfoss 084H4505

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss 084H4505 and is the answer not in the manual?

Danfoss 084H4505 Specifications

General IconGeneral
BrandDanfoss
Model084H4505
CategoryAccessories
LanguageEnglish

Related product manuals