© Danfoss A/S (AC-MCI/MWA), 2012-05 DKRCI.PD.SC0.C3.02 / 520H5687 13
Liquid Level Sensor, AKS 4100/4100U
• Connect the device to the power supply
(see the product instruction for detail on
electrical installation/connection).
• Press 3 times.
• Press
• Press
or
to select between SINGLE
or COAXIAL. Choose COAXIAL and
press to conrm.
• Press (YES) to conrm
• Press to change GAS EPS.R.
(Select the correct value from the tables
on page 16)
Press to change cursor-
position.
Press
to decrease the value or
to
increase the value.
AKS 4100
QUICK SETUP ?
YES NO
AKS 4100
PROBE TYPE
SINGLE CABLE
• Press to conrm.
• Press
to change the PROBE LENGTH.
Press
to change the position of the
cursor.
Press
to decrease the value or
to
increase the value.
Press to conrm.
• Press
to change of SCALE 4 mA.
Press
to change the cursor position.
Press
to decrease the value or
to
increase the value.
Press to conrm.
• Press
to change of SCALE 20 mA.
Press
to change the cursor position.
Press
to decrease the value or
to
increase the value.
Press to conrm.
• Wait for QUICK SETUP to complete.
Count down from 8 sec.
• Press to conrm.
• Press
or
to select between
STORE NO or STORE YES.
Press to conrm.
Default screen appears:
Quick Setup completed
You have the possibility of checking your
settings by pressing
twice.
Press to return to default screen.
Quick Setup (all values below are only examples)
• Connect the device to the power supply
• Press 3 times.
• Press
• Press
or
to select between SINGLE
or COAXIAL. Choose COAXIAL and
press to conrm.
• Press
(NO) to conrm
AKS 4100
QUICK SETUP ?
YES NO
AKS 4100
PROBE TYPE
SINGLE CABLE
• Press
to change the PROBE LENGTH.
Press
to change the position of the
cursor.
Press
to decrease the value or
to
increase the value.
Press to conrm.
• Press
to change of SCALE 4 mA.
Press
to change the cursor position.
Press
to decrease the value or
to
increase the value.
Press to conrm.
• Press
to change of SCALE 20 mA.
Press
to change the cursor position.
Press
to decrease the value or
to
increase the value.
Press to conrm.
• Wait for QUICK SETUP to complete.
Count down from 8 sec.
• Press to conrm.
• Press
or
to select between
STORE NO or STORE YES.
Press to conrm.
Default screen appears:
Quick Setup completed
AKS 4100
PROBE LENGTH
05000 mm
AKS 4100
SCALE 4 mA
04946 mm
AKS 4100
SCALE 20 mA
00070 mm
AKS 4100
QUICK SETUP
COMPLETED IN 8
AKS 4100
1.0.0
QUICK START
AKS 4100
1.0.0
STORE NO
AKS 4100
DISTANCE
5000 mm
When CO
2
is used:
For all other refrigerants:
AKS 4100
SCALE 4 mA
04946 mm
AKS 4100
SCALE 20 mA
00070 mm
AKS 4100
QUICK SETUP
COMPLETED IN 8
AKS 4100
1.0.0
STORE NO
AKS 4100
DISTANCE
5000 mm
AKS 4100
1.0.0
QUICK START
AKS 4100
PROBE LENGTH
05000 mm
COAXIAL version
AKS 4100
QUICK SETUP ?
YES NO
AKS 4100
QUICK SETUP ?
YES NO
AKS 4100
COAXIAL 2200 mm
(0 %) 4 mA 1900 mm
(100 %) 20 mA 70 mm