22 Manual RS8EN502 © Danfoss 02-2010 AK-CC 550
Digital input signal - DI3 (high voltage input)
Thecontrollerhasadigitalinput3whichcanbeusedforoneofthefollowingfunc-
tions:
O:Theinputisnotused.
1)Statusdisplayof230Vsignal
2)Doorfunction.Whentheinputis0Vitsignalsthatthedoorisopen.Therefrigera-
tionandthefansarestopped.Whenthetimesettingin“A04”ispassed,analarm
willbegivenandrefrigerationresumed.(o89)
3)Dooralarm.Whentheinputis0Vitsignalsthatthedoorisopen.Whenthetime
settingin“A04”ispassedanalarmwillbegiven.
4)Defrost.Thefunctionisstartedwithapulsesignal.(pulson230V)
5)Mainswitch.Regulationiscarriedoutwhentheinputis230V,andregulationis
stopped when the input is 0 V.
6)Nightoperation.Whentheinputis230V,therewillberegulationfornightopera-
tion.
7)Thermostatbandchangeover.Switchtothermostat2(r21)
8)Notused.
9)Notused.
10)Casecleaning.Thefunctionisstartedwithapulsesignal(pulseon230V).Seealso
description on page 5.
11)Forcedrefrigerationathotgasdefrostwhentheinputis230V.
12)Nightcover
13)Notused
14)Coolingstoppedwiththefunction"Forcedclosing"
o84 DI3cong.
Rail heat control
Therailheatcanbecontrolledinseveralways:
0: The function is not used
1:Pulsecontrolisusedwithatimerfunctionfollowingtheday/nightoperation(o41
ando42)
2:Pulsecontrolisusedwithadewpointfunction.Thisfunctionrequiresthatasignal
isreceivedaboutthedewpointvalue.Thevalueismeasuredbyasystemmanager
andsenttothecontrollerviathedatacommunication.
o85 Railh. mode
Dew point value where the rail heat is minimum
This function is discussed earlier in the manual.
o86 DewPMinlim
Dew point value where the rail heat is maximum
This function is discussed earlier in the manual.
o87 DewPMaxlim
Lowest permitted rail heat effect
Herethe%partoftheeecttobeachievedwhenthedewpointvalueisminimum.
o88 RailMinON%
Start of refrigeration when door is open
Ifthedoorhasbeenleftopen,refrigerationmustbestartedafterasettime.Thattime
can be set here.
o89 DoorInjStart
Fan for "Forced Closing"
Youcansetwhetherfansshouldbeoperationalorstoppedifthefunction"Forced
closing"isactivatedhere.
On"Noor0"thefansarestopped.
On"Yesor1"theywillbeoperational.
o90 FanForcedCl
Alternative display
A reading can be displayed by pressing the lower button on the controller. This read-
ing is set from the factory so that the defrosting stop temperature is displayed.
Adierentsettingwillgivethefollowingreading:
1:(Defroststoptemperature=factorysetting)
2:S6temperature
3:S5Btemperature(Application9only)
o92 Displ menu 2
Display of temperature during normal operation
1:Airtemperature.WeightedS3+S4
2:ProducttemperatureS6
o97 Disp. Ctrl.
Light and night blinds definition
0:Lightisswitchedoandnightblindsareopenwhenthemainswitchiso
1:Lightandnightblindsareindependentofmainswitch.
o98 LightMS=O
Configuration of the alarm relay
Thealarmrelaywillbeactivateduponanalarmsignalfromthefollowinggroups:
1-Hightemperaturealarms
2-Lowtemperaturealarms
4-Sensorerror
8-Digitalinputisactivatedforalarm
16-Defrostalarms
32-Miscellaneous
64-Injectionalarms
Thegroupsthataretoactivatethealarmrelaymustbesetbyusinganumericalvalue
whichisthesumofthegroupsthatmustbeactivated.
(E.g.avalueof5willactivateallhightemperaturealarmsandallsensorerrors)
P41 Al.Rel. Conf.