9 SERVICE menu
The SERVICE menu is for use during installation and service to optimise and adjust the operation of the heat pump. Open the menu by
pressing the left button for five seconds.
N
The menu information below describes all possible parameters. The parameters that appear in the display
vary depending on the selections made in menus (e.g. type of heat pump) and on the connected hardware
(e.g. expansion card and defrost card).
SERVICE
HOT WATER
HEAT PUMP
AUX. HEATER
MANUAL TEST
INSTALLATION
DEFROST
OPTIMUM
HGW
9.1
Sub-menu HOT WATER
Menu selection Meaning Factory setting
START Start temperature for hot water production. Shows the actual weighted hot water tem-
perature and the value within brackets indicates the start temperature. ( = no hot wa-
ter production)
(range: , 30°C /
55°C)
HOT WATER TIME Time for hot water production during combined hot water and heating demand, in mi-
nutes.
20M(range: 5M / 40M)
HEATING TIME Time for hot water production during combined heating and hot water demand, in mi-
nutes.
20M(range: 5M / 40M)
TOPH. INTERVAL Time interval between peak heating charging (anti-legionella function) in days. Operat-
ing mode that permits auxiliary heater must be selected.
7D(range: , 1D /
90D)
TOPH. TIME Time in hours that the legionella demand is to be fulfilled for legionella operation to be
considered complete.
(range: , 1M /
10M
TOPH. STOP Stop temperature for peak heat charging. Operating mode that permits auxiliary heater
must be selected.
60°C(range: 50°C /
65°C)
INFL. H.W SEN-
SOR.
Water heater sensor’s influence compared with the peak sensor’s at start of water heat-
ing.
65%(range: 0% / 100%)
WEIGHT HOT WA-
TER
The calculated value of the hot water sensor directed towards the peak sensor. -
9.2 Sub-menu HEAT PUMP
Menu selection Meaning Factory setting
INTEGRAL A1 The integral’s value for starting the heat pump. See Service instructions for more infor-
mation.
-60°min(range:
-250°min / -5°min)
HYSTERESIS If the difference between the actual supply temperature and the calculated supply tem-
perature is too great either the integral value is set to start value A1 (the heat pump
starts) or the value is set to 0 (stops the heat pump).
10°C(range: 1°C / 15°C)
MAX RETURN Stop temperature at high return from the heating system. 55°C(range: 30°C / 70°C)
START INTER-
VAL
Minimum time interval between two heat pump starts in minutes. 20M(range: 10M / 30M)
Installation Guide Domestic heat pumps
Danfoss Heating Solutions VMGFQ102
43

Other manuals for Danfoss DHP-L Opti

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss DHP-L Opti and is the answer not in the manual?

Danfoss DHP-L Opti Specifications

General IconGeneral
BrandDanfoss
ModelDHP-L Opti
CategoryHeat Pump
LanguageEnglish

Related product manuals