EasyManuals Logo
Home>Danfoss>Heat Pump>DHP-L Opti

Danfoss DHP-L Opti Installation Guide

Danfoss DHP-L Opti
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #56 background imageLoading...
Page #56 background image
10.5 Manual test
10.5.1 Introduction
Caution At manual test some heat pump controller functions are inactivated. Therefore, don´t set the heat pump into
operating conditions that can damage the installation.
Caution The installation may only be commissioned if the heating system, water heater and brine system have been
filled and bled. Otherwise the circulation pumps will be damaged.
Caution Any alarms that may occur in connection with the installation must be fault-traced.
Caution For heat pumps DHP-H Opti Pro SP and DHP-L Opti Pro SP (1-phase) it is imperative that the hot water tem-
perature changes from default setting 95 °C to 85 °C.
Caution When bleeding the circulation pumps, water can come into contact with electrical components. Therefore,
protect the electric panel against water.
10.5.2 Activate MANUAL TEST
N
Set MANUAL TEST to "2" to be able to navigate away from the menu during ongoing test operation.
1. Ensure that the main circuit breaker is on.
2.
Select operating mode , in the menu INFORMATION -> OPERAT.->
3. Open the SERVICE menu by pressing and holding <- (left button) for five seconds.
4. Set the value for MANUAL TEST to 2.
Installation Guide
Domestic heat pumps
VMGFQ102 Danfoss Heating Solutions
56

Other manuals for Danfoss DHP-L Opti

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss DHP-L Opti and is the answer not in the manual?

Danfoss DHP-L Opti Specifications

General IconGeneral
BrandDanfoss
ModelDHP-L Opti
CategoryHeat Pump
LanguageEnglish

Related product manuals