User manual ERC 113 refrigeration controller
Power Supply 100 - 240 VAC (±10%), switch mode power supply
Rated Power
Average 0.7 W
5 Inputs: 4 Analogue & Digital, 1 Digital; user specific assignment
Input
• Air/Evaporator/Condenser
• Door sensor:
all types, user specific
• Motion sensor
• Light sensor:
Danfoss ECO light sensor
• DP: for remote
communication
Output
UL60730 EN60730
"DO1" (Compressor relay)
120 V a.c.: 16 A resistive/FLA16/LRA72
240 V a.c.: 10 A resistive/FLA10/LRA60
16(16) A
"DO4" 8 A resistive, FLA2/LRA12, TV-1 8 A resistive, 2(2) A
"DO5" FLA2/LRA12, TV-1 8 A resistive, 2(2) A
"DO6" FLA2/LRA12, TV-1 8 A resistive, 2(2) A
Max 10 A total "DO4-6"
Probes
Danfoss NTC sensors and Danfoss ECO accessories (300 - 3,000 mm)
Danfoss PT1000 ohm/0°C
Connectors
Modular connector system for OEM customers, with optional output screw terminal adapter;
Input connector type: Rast2.5 Edge connectors; Output connector type: RAST 5 Standard
Programming Programming with Danfoss ERC docking station, integrated system
Assembly Self-drilling screws or plastic quick fasteners
Keypad Only with RDI 107: 4 buttons (integrated IP65 design), 2 left, 2 right; user programmable
Operating Conditions 0 °C to 55 °C. 93% rH
Storage Conditions -40 °C to 85 °C, 93% rH
Range of Measurement -40 °C to 85 °C
Protection Water and dust protection corresponds to IP31, accessibility of connectors limit rear part rating to IP00
Environmental Pollution degree II, non-condensing
Resistance to heat & fire Category D (UL94-V0)
EMC category Category I
Operating Cycles Compressor relay: more than 175,000 at full load (16A(16A))
Approvals
R290/R600a end-use applications employing in
accordance to EN/IEC 60335-2-24, annex CC and EN/IEC
60335-2-89, annex BB
Glow wire according to EN/IEC 60335-1
IEC/EN 60730
UL60730
NSF
GOST R 60730
These approvals are only valid when using the accessories
approved
Technical specs
IMPORTANT NOTE
The inputs are not galvanic separated and are connected directly to the mains supply!
For that reason, door-switches, sensors as well as the cables must fulfil the reinforced insulation requirements.
Produced by Danfoss A/S (ADAP-KOOL®) | 2016-07
23
DKRCC.ES.RL0.F5.02

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss ERC 113C and is the answer not in the manual?

Danfoss ERC 113C Specifications

General IconGeneral
BrandDanfoss
ModelERC 113C
CategoryController
LanguageEnglish

Related product manuals