User manual ERC 113 refrigeration controller
Configuration of inputs and outputs
ERC 113 inputs and outputs
Possible input and output
connections
The ERC 113 inputs and outputs are configurable
by the customer. Before getting started it is a
good idea to check if all inputs are configured
correctly and match the sensors attached.
Input and output configuration settings are part
of the assignment menu "ASi".
NOTE: Coded sensors will impact on the number of
possible configurations
Inputs/outputs Stand-alone With remote display
RDI 107
With remote spindle
RSP 01
Sensor 1 X X X
Sensor 2 X X X
Sensor 3 X X
Sensor 4 X X X
Sensor 5 X
Sensor 7 X
Relay 2 X X X
Relay 3 X X X
Relay 4 X X X
Relay 5 X
DI (not com) X X
The table shows the possible input and output connections for the three application setups:
ERC 113 stand-alone, ERC 113 + remote display and ERC 113 + remote spindle.
For instance:
Danfoss supplies only 2-pole defrost sensors, so
input "S3" will most likely be used as a
defrost/evaporator temperature sensor input.
Please contact your local Danfoss representative
for information about default settings.
NOTE: remote display is always connected to the
digital input "Di" an d configured as "buS", whilst
remote spindle is always connected to "S3" and
configured as "rSp"
Produced by Danfoss A/S (ADAP-KOOL®) | 2016-07
5
DKRCC.ES.RL0.F5.02

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss ERC 113C and is the answer not in the manual?

Danfoss ERC 113C Specifications

General IconGeneral
BrandDanfoss
ModelERC 113C
CategoryController
LanguageEnglish

Related product manuals