Conguration
Menu navigation and overview
Table 5: Key functions
Scroll up: Short press (less than 1 second)
Main switch ON/OFF : Press and hold (~ 3 seconds)
Factory reset: Press and hold at Power up
Scroll down: Short press (Less than 1 sec.)
Defrost Start/Stop : Press and hold (~3 secs.)
Back function : Short press (less than 1 sec.)
Pull down start / stop : Press and hold (~3 secs.)
Set point change or OK : Short press (Less than 1 sec.)
Enter Menu : Press and hold (~ 3 secs.)
Table 6: Display icons
Night mode (Energy saving)
Fan running
Compressor running (Flashes in pull-down mode)
Active alarm
Defrost
Unit (°C or °F)
Quick conguration at power up
STEP 1: power on
STEP 2: select the quick conguration menu
Within 30 seconds of power on, press “<” BACK for 3 seconds. The main switch “r12” is automatically set to OFF.
STEP 3: select pre-installed application o61
The display automatically shows the application selection parameter “o61”.
Press SET to select the pre-installed application.
The display shows the default value (eg. “AP0” ashing).
Choose the application type by pressing UP/DOWN and press SET to conrm.
The controller presets parameter values according to the selected application and does not hide relevant
parameters.
Tip: you can easily move from AP0 to AP6, and thus select the simplied list of parameters, by pressing the UP key
(circular list).
STEP 4: select sensor type “o06
The display automatically shows sensor selection parameter “o06”.
Press SET to select the sensor type.
The display shows the default value (eg. “n10” ashing).
Choose sensor type by pressing UP/DOWN (n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000) and press SET to
conrm.
NOTE:
All sensors must be the same type.
STEP 5: congure DO4 output “o36”
The display automatically shows the o36 parameter to congure “DO4” output. (Available only in 4 relays model).
Select light “Lig” or alarm “ALA” as per the application and press SET to conrm.
The display returns to normal display mode and the control is started.
NOTE:
Refer Pre-dened applications for a complete description of the available applications.
Electronic refrigeration control, type ERC 21X
© Danfoss | Climate Solutions | 2023.01 BC194286421698en-000901 | 14