Function
Code
Min.
Max.
Unit
AP0
AP1
AP2
AP3
AP4
AP5
AP6
AP7
Main switch ( -1=Service, 0=OFF, 1=ON,)
r12
-1
1
1
1
1
1
1
1
1
1
Night Set back
r13
-50.0
50.0
K
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Reference displacement oset temperature
r40
-50.0
20.0
°C
0.0
0.0
0.0
0.0
0.0
0.0
-
0.0
Pull down duration
r96
0
960
min
0
0
0
0
0
0
-
-
Pull down limit temperature
r97
-100.0
200.0
°C
0.0
0.0
0.0
0.0
0.0
0.0
-
-
Alarm
Table 31: Alarm
Function
Code
Min.
Max.
Unit
AP0
AP1
AP2
AP3
AP4
AP5
AP6
AP7
Alarm
A--
Delay for temp alarm during normal conditions
A03
0
240
min
30
45
30
30
30
30
30
10
Delay for temp alarm during pull-down/start up/
defrost
A12
0
240
min
60
90
60
60
60
60
60
-
High temp. alarm limit
A13
-100.0
200.0
°C
8.0
10.0
8.0
-15.0
8.0
-15.0
8.0
80.0
Low temp. alarm limit
A14
-100.0
200.0
°C
-30.0
0.0
-2.0
-30.0
-2.0
-30.0
-30.0
20.0
DI1 delay (Time delay for selected DI1 function)
A27
0
240
min
30
30
30
30
30
30
30
30
DI2 delay (Time delay for selected DI2 function)
A28
0
240
min
30
30
30
30
30
30
30
30
Condenser High alarm limit
A37
0
200
°C
80
80
80
80
80
80
-
-
Condenser High block limit
A54
0
200
°C
85
85
85
85
85
85
-
-
Voltage protection
A72
no
YES
no
no
no
no
no
no
no
no
Minimum cut-in voltage
A73
0
270
V
0
0
0
0
0
0
0
0
Minimum cut-out voltage
A74
0
270
V
0
0
0
0
0
0
0
0
Maximum voltage
A75
0
270
V
270
270
270
270
270
270
270
270
Defrost
Table 32: Defrost
Function
Code
Min.
Max.
Unit
AP0
AP1
AP2
AP3
AP4
AP5
AP6
AP7
Defrost
d--
Defrost Method (no=None, nAt=Natural, EL = Elec-
tric; gAS=Hot gas)
d01
no
gAS
EL
nAt
EL
EL
EL
EL
EL
-
Defrost stop temperature.
d02
0.0
50.0
°C
6.0
-
-
-
6.0
6.0
6.0
-
Defrost Interval
d03
0
240
hour
8
6
8
12
8
12
8
-
Max defrost Time
d04
0
480
min
30
45
15
15
30
30
30
-
Defrost delay at power up (or DI signal)
d05
0
240
min
0
0
0
0
0
0
-
-
Drip delay
d06
0
60
min
0
0
0
0
0
0
2
(1)
-
Fan delay after defrost
d07
0
60
min
0
0
0
0
0
0
5
(1)
-
Fan start temperature after defrost
d08
-50.0
50.0
°C
-5.0
50.0
(1)
50.0
(1)
50.0
(1)
-5.0
-5.0
NA
-
Fan during defrost
d09
OFF
on
on
on
OFF
OFF
OFF
OFF
OFF
-
Defrost stop sensor
d10
non
dEF
non
non
(1)
non
(1)
non
(1)
dEF
(1)
dEF
(1)
non
-
Accumulated Compressor runtime to start defrost
(0=OFF)
d18
0
96
hour
0
0
0
0
0
0
-
-
Defrost on demand (20=OFF)
d19
0.0
20.0
K
20.0
-
-
-
20.0
20.0
-
-
Defrost delay after pull down cycle
d30
0
960
min
0
0
0
0
0
0
-
-
(1)
This option is a default setting in the controller and cannot be changed.
(1)
This option is a default setting in the controller and cannot be changed.
Fan control
Table 33: Fan control
Function
Code
Min.
Max.
Unit
AP0
AP1
AP2
AP3
AP4
AP5
AP6
AP7
Fan control
F--
Fan at compressor cutout
F01
FAo
FPL
FAo
FAo
FAo
FAo
FAo
FAo
FAo
FAo
Fan stop evap. Temperature
F04
-50.0
50.0
°C
50.0
-
-
-
50.0
50.0
50.0
(1)
-
Fan ON Cycle
F07
0
180
min
2
2
2
2
2
2
2
(1)
2
Fan OFF cycle
F08
0
180
min
2
2
2
2
2
2
2
(1)
2
(1)
This option is a default setting in the controller and cannot be changed.
(1)
This option is a default setting in the controller and cannot be changed.
Electronic refrigeration control, type ERC 21X
© Danfoss | Climate Solutions | 2023.01 BC194286421698en-000901 | 28