Parameters
Menu functions
Conguration
Table 7: Conguration
Code
Parameter description
Min.
Max.
Unit
cFg
Conguration
r12
Main Switch
With this setting refrigeration can be started, stopped or a manual override of the outputs can be allowed.
Service (manual control of outputs allowed)(-1 in Controller Display)
OFF (0 in Controller Display)
ON (1 in Controller Display)
Service
ON
o61
Predened applications
Predened applications is to give the user an easy and fast way to congure the controller. Users can set appropriate applica-
tion that meets their requirements under this menu (please refer predened applications table under section 2.4 for more
details). Predened application is protected by main switch.
AP0
AP7
o07
Select main application type for which controller is used
rE= Cooling
Ht= Heating
rE
Ht
o06
Sensor type
This parameter denes the type of temperature sensors connected to the controller. Below sensor types can be used in
ERC21x
n5=NTC 5K (5000 Ohm at 25 °C, Beta value=3980 @25/100 °C)
n10= NTC 10 (10000 Ohm at 25 °C, Beta value = 3435 @ 25/100 °C)
pt1= PT1000
ptc= PTC
All the mounted sensors (Sair, S5 and Sc)must be of same type.
n10
pt1
o71
This parameter denes the desired conguration for Relay 2 (DO2)
dEF=Defrost
ALA=alarm
Lig=Light
dEF
Lig
o36
This parameter denes the desired conguration for Relay 4 (DO4). Applicable only for ERC214.
Lig=Light
ALA=alarm
Lig
ALA
Thermostat
Table 8: Thermostat
Code
Parameter description
Min.
Max.
Unit
r--
Thermostat
r00
SetPoint
This parameter denes the desired cabinet temperature at which compressor cuts out. The set point can be locked to a range
within r02 and r03 settings.
-100.0
200.0
°C
r01
Dierential
This denes the dierence between the cut-out and the cut-in of compressor relay. Compressor relay will cut-in when the
cabinet temperature reaches the set point+ dieretial. In case of heating application, heater will cut-in when the temperature
reaches the set point-dierential.
0.1
20.0
K
r02
Maximum Set Point limitation
The maximum allowable setpoint value can be congured here that would avoid setting too high values by mistake.
-100.0
200.0
°C
r03
Minimum Set Point limitation
The minimum allowable setpoint value can be congured here that would avoid setting too low values by accident/mistake.
-100.0
200.0
°C
r04
Display
oset
Correction value in display temperature. If the temperature of the products / cabinet and the temperature received by the
controller are not identical, an oset adjustment of the display temperature can be carried out using this parameter.
-10.0
10.0
K
r05
Display Unit
Set here if the controller is to show temperature values in °C or in °F. Switching from one to the other will cause all tempera-
ture settings to be automatically updated to respective unit.
-C
-F
r09
Calibration of Sair
This parameter is a relative value and allows adjustment of the Sair sensor temperature. For instance, at a measured tempera-
ture of 7 °C and r09 set to 2K, the input from the Sair sensor will be 9 °C instead.
-20.0
20.0
K
r12
Main Switch
With this setting refrigeration can be started, stopped or a manual override of the outputs can be allowed. Stopped refrigera-
tion will give a “OFF” signal on the display.
-1=service (manual control of outputs allowed)
0=OFF
1=ON
-1
1
r13
Night setback value
The thermostat’s reference can be oset by this value during night or when there is no usage. Oset can be set both possitive
and negative sides (Select a negative value if there is to be cold accumulation). Activation can take place via digital input.
-50.0
50.0
K
Electronic refrigeration control, type ERC 21X
© Danfoss | Climate Solutions | 2023.01 BC194286421698en-000901 | 18