EasyManuals Logo
Home>Danfoss>Media Converter>FC 100 Series

Danfoss FC 100 Series User Manual

Danfoss FC 100 Series
149 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #109 background imageLoading...
Page #109 background image
7.3.15 15-** Drive Information
Par. No.
#
Parameter description Default value 4-set-up Change
during
operation
Conver-
sion index
Type
15-0* Operating Data
15-00 Operating Hours 0 h All set-ups FALSE 74 Uint32
15-01 Running Hours 0 h All set-ups FALSE 74 Uint32
15-02 kWh Counter 0 kWh All set-ups FALSE 75 Uint32
15-03 Power Up's 0 N/A All set-ups FALSE 0 Uint32
15-04 Over Temp's 0 N/A All set-ups FALSE 0 Uint16
15-05 Over Volt's 0 N/A All set-ups FALSE 0 Uint16
15-06 Reset kWh Counter [0] Do not reset All set-ups TRUE - Uint8
15-07 Reset Running Hours Counter [0] Do not reset All set-ups TRUE - Uint8
15-08 Number of Starts 0 N/A All set-ups FALSE 0 Uint32
15-1* Data Log Settings
15-10 Logging Source 0 2 set-ups TRUE - Uint16
15-11 Logging Interval SR 2 set-ups TRUE -3 TimD
15-12 Trigger Event [0] False 1 set-up TRUE - Uint8
15-13 Logging Mode [0] Log always 2 set-ups TRUE - Uint8
15-14 Samples Before Trigger 50 N/A 2 set-ups TRUE 0 Uint8
15-2* Historic Log
15-20 Historic Log: Event 0 N/A All set-ups FALSE 0 Uint8
15-21 Historic Log: Value 0 N/A All set-ups FALSE 0 Uint32
15-22 Historic Log: Time 0 ms All set-ups FALSE -3 Uint32
15-23 Historic Log: Date and Time SR All set-ups FALSE 0 TimeOfDay
15-3* Alarm Log
15-30 Alarm Log: Error Code 0 N/A All set-ups FALSE 0 Uint8
15-31 Alarm Log: Value 0 N/A All set-ups FALSE 0 Int16
15-32 Alarm Log: Time 0 s All set-ups FALSE 0 Uint32
15-33 Alarm Log: Date and Time SR All set-ups FALSE 0 TimeOfDay
15-4* Drive Identification
15-40 FC Type 0 N/A All set-ups FALSE 0 VisStr[6]
15-41 Power Section 0 N/A All set-ups FALSE 0 VisStr[20]
15-42 Voltage 0 N/A All set-ups FALSE 0 VisStr[20]
15-43 Software Version 0 N/A All set-ups FALSE 0 VisStr[5]
15-44 Ordered Typecode String 0 N/A All set-ups FALSE 0 VisStr[40]
15-45 Actual Typecode String 0 N/A All set-ups FALSE 0 VisStr[40]
15-46
Frequency Converter Ordering
No
0 N/A All set-ups FALSE 0 VisStr[8]
15-47 Power Card Ordering No 0 N/A All set-ups FALSE 0 VisStr[8]
15-48 LCP Id No 0 N/A All set-ups FALSE 0 VisStr[20]
15-49 SW ID Control Card 0 N/A All set-ups FALSE 0 VisStr[20]
15-50 SW ID Power Card 0 N/A All set-ups FALSE 0 VisStr[20]
15-51
Frequency Converter Serial
Number
0 N/A All set-ups FALSE 0 VisStr[10]
15-53 Power Card Serial Number 0 N/A All set-ups FALSE 0 VisStr[19]
15-55 Vendor URL 0 N/A All set-ups FALSE 0 VisStr[40]
15-56 Vendor Name 0 N/A All set-ups FALSE 0 VisStr[40]
15-6* Option Ident
15-60 Option Mounted 0 N/A All set-ups FALSE 0 VisStr[30]
15-61 Option SW Version 0 N/A All set-ups FALSE 0 VisStr[20]
15-62 Option Ordering No 0 N/A All set-ups FALSE 0 VisStr[8]
15-63 Option Serial No 0 N/A All set-ups FALSE 0 VisStr[18]
How to Programme the Frequ...
VLT
®
HVAC Drive Operating Instructions
MG.11.AD.02 - VLT
®
is a registered Danfoss trademark 109
7
7

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss FC 100 Series and is the answer not in the manual?

Danfoss FC 100 Series Specifications

General IconGeneral
BrandDanfoss
ModelFC 100 Series
CategoryMedia Converter
LanguageEnglish

Related product manuals