5.2 Application Examples
5.2.1 Start/Stop
Terminal 18 = start/stop par. 5-10 Terminal 18 Digital Input [8]
Start
Terminal 27 = No operation par. 5-12 Terminal 27 Digital Input
[0] No operation (Default coast inverse
Par. 5-10 Terminal 18 Digital Input = Start (default)
Par. 5-12 Terminal 27 Digital Input = coast inverse
(default)
Illustration 5.4: Terminal 37: Available only with Safe Stop
Function!
5.2.2 Pulse Start/Stop
Terminal 18 = start/stop par. 5-10 Terminal 18 Digital Input [9]
Latched start
Terminal 27= Stop par. 5-12 Terminal 27 Digital Input [6] Stop
inverse
Par. 5-10 Terminal 18 Digital Input = Latched start
Par. 5-12 Terminal 27 Digital Input = Stop inverse
Illustration 5.5: Terminal 37: Available only with Safe Stop
Function!
Commissioning and Applicati...
VLT
®
HVAC Drive Operating Instructions
52 MG.11.AD.02 - VLT
®
is a registered Danfoss trademark
5