7.3.23 25-** Cascade Pack Controller
Par. No. # Parameter description Default value 4-set-up Change during
operation
Conver-
sion index
Type
25-0* System Settings
25-00 Cascade Controller [0] Disabled 2 set-ups FALSE - Uint8
25-02 Motor Start [0] Direct on Line 2 set-ups FALSE - Uint8
25-04 Pump Cycling [0] Disabled All set-ups TRUE - Uint8
25-05 Fixed Lead Pump [1] Yes 2 set-ups FALSE - Uint8
25-06 Number of Pumps 2 N/A 2 set-ups FALSE 0 Uint8
25-2* Bandwidth Settings
25-20 Staging Bandwidth 10 % All set-ups TRUE 0 Uint8
25-21 Override Bandwidth 100 % All set-ups TRUE 0 Uint8
25-22 Fixed Speed Bandwidth
casco_staging_bandwidt
h (P2520)
All set-ups TRUE 0 Uint8
25-23 SBW Staging Delay 15 s All set-ups TRUE 0 Uint16
25-24 SBW Destaging Delay 15 s All set-ups TRUE 0 Uint16
25-25 OBW Time 10 s All set-ups TRUE 0 Uint16
25-26 Destage At No-Flow [0] Disabled All set-ups TRUE - Uint8
25-27 Stage Function [1] Enabled All set-ups TRUE - Uint8
25-28 Stage Function Time 15 s All set-ups TRUE 0 Uint16
25-29 Destage Function [1] Enabled All set-ups TRUE - Uint8
25-30 Destage Function Time 15 s All set-ups TRUE 0 Uint16
25-4* Staging Settings
25-40 Ramp Down Delay 10.0 s All set-ups TRUE -1 Uint16
25-41 Ramp Up Delay 2.0 s All set-ups TRUE -1 Uint16
25-42 Staging Threshold SR All set-ups TRUE 0 Uint8
25-43 Destaging Threshold SR All set-ups TRUE 0 Uint8
25-44 Staging Speed [RPM] 0 RPM All set-ups TRUE 67 Uint16
25-45 Staging Speed [Hz] 0.0 Hz All set-ups TRUE -1 Uint16
25-46 Destaging Speed [RPM] 0 RPM All set-ups TRUE 67 Uint16
25-47 Destaging Speed [Hz] 0.0 Hz All set-ups TRUE -1 Uint16
25-5* Alternation Settings
25-50 Lead Pump Alternation [0] Off All set-ups TRUE - Uint8
25-51 Alternation Event [0] External All set-ups TRUE - Uint8
25-52 Alternation Time Interval 24 h All set-ups TRUE 74 Uint16
25-53 Alternation Timer Value 0 N/A All set-ups TRUE 0 VisStr[7]
25-54 Alternation Predefined Time SR All set-ups TRUE 0
TimeOfDayWo-
Date
25-55 Alternate if Load < 50% [1] Enabled All set-ups TRUE - Uint8
25-56 Staging Mode at Alternation [0] Slow All set-ups TRUE - Uint8
25-58 Run Next Pump Delay 0.1 s All set-ups TRUE -1 Uint16
25-59 Run on Mains Delay 0.5 s All set-ups TRUE -1 Uint16
25-8* Status
25-80 Cascade Status 0 N/A All set-ups TRUE 0 VisStr[25]
25-81 Pump Status 0 N/A All set-ups TRUE 0 VisStr[25]
25-82 Lead Pump 0 N/A All set-ups TRUE 0 Uint8
25-83 Relay Status 0 N/A All set-ups TRUE 0 VisStr[4]
25-84 Pump ON Time 0 h All set-ups TRUE 74 Uint32
25-85 Relay ON Time 0 h All set-ups TRUE 74 Uint32
25-86 Reset Relay Counters [0] Do not reset All set-ups TRUE - Uint8
25-9* Service
25-90 Pump Interlock [0] Off All set-ups TRUE - Uint8
25-91 Manual Alternation 0 N/A All set-ups TRUE 0 Uint8
How to Programme the Frequ...
VLT
®
HVAC Drive Operating Instructions
MG.11.AD.02 - VLT
®
is a registered Danfoss trademark 121
7
7

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss FC 100 Series and is the answer not in the manual?

Danfoss FC 100 Series Specifications

General IconGeneral
BrandDanfoss
ModelFC 100 Series
CategoryMedia Converter
LanguageEnglish

Related product manuals