Status/Read Outs Parameters
Description and selection
options
Alterna‐
tive
Modbus
address
Pass‐
word
level to
Read -
Write
Read
only
(RO) /
Read
Write
(RW) /
Write
(W)
Readout the main switch
state of ICAD.
2: cong;
1: manual;
0: auto
Readout ICAD mode
2: 3 – point;
1: on/o;
0: modulating
Readout the valve congura-
tion for ICAD.
12: ICADTS ICMTS 50/80;
11: ICADTS ICMTS20;
10: Pilot Valve CVE;
9: ICAD1200B ICM150;
8: ICAD1200B ICM125;
7: ICAD1200B ICM100;
6: ICAD1200B ICM65;
5: ICAD1200B ICM50;
4: ICAD1200B ICM40;
3: ICAD600B ICM32;
2: ICAD600B ICM25;
1: ICAD600B ICM20;
0: not congured
Readout the analog input
when the operation mode
(ID2) is set to modulating
and the input signal (ID3) is
set to use current (0-20mA
or 4-20mA) 0…22000 points,
where 1000 = 1mA (I.e.
10031 = 10.031mA; 7062 =
7.062mA)
Readout the analog input
when the operation mode
(ID2) is set to modulating
and the input signal (ID3) is
set to use voltage (0-10V or
2-10V) 0…12000 points,
where 1000 = 1V (I.e. 1291 =
1.291V; 10372 = 10.372V)
Readout the analog output
when AO signal output
(ID18) is set to use (0-20mA
or 4-20mA) 0…22000 points,
where 1000 = 1mA (I.e.
10031 =10.031mA; 7062 =
7.062mA)
Readout of Uninterruptible
Power Supply (UPS) is ap-
plied to the ICAD. This ena-
bled A4 alarms (Low voltage
of UPS supply). 1: yes;
0: no
Readout of the requested
valve position for safe state.
Safe state occurs for A2, A3,
A5, A8, A10, and can be a re-
sult of the boosting process
during A9. 3: emergency
opening degree (set posi-
tion to ID27)
2: maintain position;
1: open valve;
0: close valve;
© Danfoss | Climate Solutions | 2024.01 BC465027827472en-000102 | 29