Air Handling seq. - user manual
6.4| Main setpoint
MAIN SETPOINT
SET Setpoint Min Max Default U.M. Text value
MST Main Setpoint
STH Setpoint heat -15,0 90,0 21,0 °C
STC Setpoint cool -15,0 90,0 21,0 °C
HUM Min setpoint humidity 0 100,0 40,0 %
DEH Max setpoint humidity 0 100,0 60,0 %
EST Economy Setpoint
ES1 Economy set enable 1 2 NO NO;YES
ES2 Oset set heat economy -15,0 90,0 -3,0 °C
ES3 Oset set cool economy -15,0 90,0 2,0 °C
COM TempCompensation
TC1 Probe selection 1 8 OUt NO;SUP;REt;OUt;tH1;tH2;tC1;tC2
TC2 Winter end temperature -15,0 90,0 -5,0 °C
TC3 Winter start temperature -15,0 90,0 5,0 °C
TC4 Winter oset -10,0 10,0 -2,0 K
TC5 Summer start temperature -15,0 90,0 31,0 °C
TC6 Summer end temperature -15,0 90,0 38,0 °C
TC7 Summer oset -10,0 10,0 7,0 K
Tab 26_ [Temperature control sequences - Main setpoint]
The main temperature setpoint are STH for heating and STC for cooling temperature control.
The active temperature setpoint (hereafter ATS) is then:
ATS=STH in heating
ATS=STC in cooling
Through parameters D02, D03, H12, H22, C12, they can be assigned to the specic sequence,
(see “6] Temperature control sequences”).
The main humidity setpoint are HUM for humidifying and DEH for dehumidifying control.
Main setpoint are accessible from the user interface in an shorten way, by pressing the DOWN key for 3 seconds.
Main setpoint are aected by economy mode and temperature compensation
6.4.1| Economy mode
The economy mode can be enabled by ES1=YES or via digital input “COE – Comf/Eco”.
By enabling the economy mode, the main temperature setpoint are changed by ES2 and ES3 quantity.
The Active Temperature Setpoint (ATS) becomes:
ATS=STH+ES2 in heating
ATS=STC+ES3 in cooling