Air Handling seq.- user manual
DKRCC.PS.RI.A1.02 / 520H4358 - Air Handling Seq. user manual - V 2.2
Produced by Danfoss Electronics spa Graphic Department, 10-2009
51
12| Supply and return fans
SUPPLY AND RETURN FANS
FAN Fans Min Max Default U.M. Text value
GEN General
F00 Fan control type 1 3 ONOF ;ONOF;REQ;PId
F01 Probe selection 1 3 SUP ;SUP;REt;bAR
F02 Minimum speed 0,0 F03 0,0 %
F03 Maximum speed F02 100,0 100,0 %
F04 Coils OFF with fan OFF 1 2 NO ;NO;YES
F05 Stop fans for antifreeze 1 2 YES ;NO;YES
SUF Supply Fan
SF1 Time at maximum speed at
startup
0 9999 0 SEC
SF2 Anti resonance 0,0 100,0 0,0 %
SF3 Anti resonance zone 0,0 50,0 0,0 %
SF4 Fan delay at startup 0 9999 5 SEC
SF5 Fan delay at OFF 0 9999 5 SEC
REF Return Fan
RF1 Time at maximum speed at
startup
0 9999 0 SEC
RF2 Anti resonance 0,0 100,0 0,0 %
RF3 Anti resonance zone 0,0 50,0 0,0 %
RF4 Fan delay at startup 0 9999 5 SEC
RF5 Fan delay at OFF 0 9999 5 SEC
REG PID Regulation
Fr1 Action of regulation 1 4 DIR ;INV;dIR;CO1;CO2
Fr2 Setpoint -15,0 110,0 12,0
Fr3 Proportional band 0,1 20,0 2,0
Fr4 Integral time 0 9999 0 SEC
Fr5 Derivative time 0 9999 0 SEC
Tab 38_ [Supply and return fans - Supply and return fans]
The type of supply fan control is dened using parameter F00.
The return fan, if present, is assumed to be controlled as the supply fan.
Each fan functions only if its dampers are open.
12.1| Type of supply and return fans
The parameters that enable setting the way fan is controlled is F00 – Fan control type.
If F00=ONOF, the fan is an ON/OFF unit, it starts when the unit is turned on (after delay time SF4 has
elapsed) and always remains on except in the case of fan alarms, re and antifreeze (see “12.3] Fans and
antifreeze”).
The fan is controlled using the digital output “SUF - Supply Fan”.
If F00=REQ, the fan is only activated when temperature or humidity control action is requested.
The following 3 digital outputs are used to control the fan; they have been conceived to run a fan with a
star-delta connection arranged for 2 operating speeds.
“SUF - Supply Fan” – is activated when a control action is requested (line contactor)
“SFL - SupplyFanLow.” – is activated as indicated in the gure (star contactor)
“SFH - SupplyFanHigh.” – is activated as indicated in the gure (delta contactor)
Then the analog output “SUF - Supply Fan” is used, activated in a manner proportional to the demand.
»
»