EasyManuals Logo
Home>Danfoss>Controller>OPTYMA Control

Danfoss OPTYMA Control User Manual

Danfoss OPTYMA Control
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #3 background imageLoading...
Page #3 background image
User Guide | Optyma™ control AK-RC 113 three phase
© Danfoss | DCS (vt) | 2020.03 BC317523579312en-000101 | 3
1.0 Introduction
1.1 General
The OPTYMA™ Control three-phase is a controller for refrigeration systems with a three-phase
compressor or for controlling the three-phase evaporating unit only, for complete cold room
management. Front access to the automatic fuse and motor protector for the compressor and an
innovative design combine to make it the ideal choice for effective refrigeration control.
Applications:
Complete management of three-phase refrigerating systems up to 7.5 HP static or ventilated, with
off-cycle or electrical defrosting.
2.0 Technical
Characteristics
2.1 Product ID Codes Line of electrical panel of OPTYMA
TM
Control (4 HP):
Line of electrical panel of OPTYMA
TM
Control (7 HP):
Code Numbers
Identification codes Compressor motor circuit breaker range
080Z3221 4,5 – 6,3 A
080Z3222 7 – 10 A
Code Numbers
Identification codes Compressor motor circuit breaker range
080Z3226 11 – 16 A
080Z3227 14 – 20 A
2.2 Product Series –
Technical Characteristics
Technical characteristics OPTYMA
TM
Control (4 HP) OPTYMA
TM
Control (7.5 HP)
Box dimensions 400 x 300 x 135 mm 400 x 300 x 135 mm
Weight 9 kg 10 kg
Protection rating IP 65 IP 65
Power supply (3F+N+T) 400 V AC ±10% 50/60Hz 400 V AC ±10% 50/60Hz
Load type 3-phase 3-phase
Operating temperature - 5 – 40 °C - 5 – 40 °C
Storage temperature -25 – 55 °C -25 – 55 °C
Relative ambient humidity from 30% to 95% RH
w/out condensate
from 30% to 95% RH
w/out condensate
Altitude < 1000 m < 1000 m
Main switch / general protection
Interruption power
4 poles magnetothermic 16A “D”
Icn=6kA / Ics=8kA / Icu=15kA
4 poles magnetothermic 25A “D”
Icn=6kA / Ics=8kA / Icu=15kA
Compressor protection Adjustable motor circuit breaker Adjustable motor circuit breaker
Defrosting Electrical Electrical
Status indicators LED + display LED + display
Alarm signals LED + buzzer LED + buzzer
Inputs
Ambient probe NTC 10K 1% NTC 10K 1%
Evaporator probe NTC 10K 1% NTC 10K 1%
Door switch Present Present
High/low pressure switch Present Present
Kriwan® connection Present Present
Compressor functioning mode selection Pump-down / thermostat Pump-down / thermostat
Outputs
Compressor See motor circuit breaker thermal
range relative to panel ID code
See motor circuit breaker thermal
range relative to panel ID code
Condenser fans output 1
800 W (1 phase) 800 W total (1 phase)
Condenser fans output 2 (separated)
Evaporator fans 500 W (1 phase) 2000 W (1phase / 3 phases)
Defrosting heaters 6000 W (AC1) eq. resistive load 9000 W (AC1) eq. resistive load
Room light 800 W (AC1) resistive load 800 W (AC1) resistive load
Solenoid valve Present Present
Compressor oil heater Present Present
Aux1 100 W 100 W
Aux2 100 W 100 W
Supervision system Modbus Modbus