Control card, analog output:
Number of programmable analog outputs 1
Terminal number 42
Current range at analog output 0/4 - 20 mA
Max. load to common at analog output
500
Accuracy on analog output Max. error: 1.5 % of full scale
Resolution on analog output 10 bit
The analog output is galvonically isolated from the supply voltage (PELV) and other high-voltage terminals. See
section entitled Galvonic Isolation.
Control card, 24 V DC output:
Terminal number 12
Max. load 130 mA
The 24 V DC supply is galvanically isolated from the supply voltage (PELV) , but has the same potential as the analog
and digital inputs and outputs. See section entitled Galvanic Isolation.
Control card, 10 V DC output:
Terminal number 50
Output voltage 10.5 V ±0.5 V
Max. load 15 mA
The 10 V DC supply is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals. See
section entitled Galvanic Isolation.
Control card, RS-485 serial communication:
Terminal number 68 (TX+, RX+), 69 (TX-, RX-)
Terminal number 67 + 5 V
Terminal number 70 Common for terminals 67, 68 and 69
Full galvanic isolation. See section entitled Galvanic Isolation.
For CANopen/DeviceNet units, see VLT 2800 DeviceNet manual, MG.90.BX.YY.
Relay outputs:
1)
Number of programmable relay outputs 1
Terminal number, control card (resistive and inductive load) 1-3 (break), 1-2 (make)
Max. terminal load (AC1) on 1-3, 1-2, control card 250 V AC, 2 A, 500 VA
Max. terminal load (DC1 (IEC 947)) on 1-3, 1-2, control card 25 V DC, 2 A /50 V DC, 1A, 50W
Min. terminal load (AC/DC) on 1-3, 1-2, control card 24 V DC 10 mA, 24 V AC 100 mA
The relay contact is separated from the rest of the circuit by strengthened isolation.
Note: Rated values resistive load - cosphi >0.8 for up to 300,000 operations.
Inductive loads at cosphi 0.25 approximately 50% load or 50% life time.
VLT
®
2800 Series
MG.27.A2.22 - VLT
®
is a registered Danfoss trademark 107
All about VLT 2800

Table of Contents

Other manuals for Danfoss VLT 2800 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 2800 Series and is the answer not in the manual?

Danfoss VLT 2800 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT 2800 Series
CategoryDC Drives
LanguageEnglish

Related product manuals