Warning word [Hex] gives one or several warnings in
hex code. See Serial communication in the VLT 2800
Design Guide for further information.
Extended status word [Hex] gives one or several status
modes in Hex code. See Serial communication in the
VLT 2800 Design Guide for further information.
Communication option card warning [Hex] gives a
warning word if there is a fault in the communication
bus. Only active if communication options are instal-
led.
If there are no communication options 0 Hex is dis-
played.
Pulse count gives the number of pulses that the unit
has registered.
010 Small display line 1.1
(DISPLAY LINE 1.1)
Value:
See par. 009 Large display
readout
Analog input 53
[V] [17]
Function:
In this parameter, the first of three data values can be
selected that is to be displayed in the LCP control unit
display, line 1, position 1. This is a useful function, e.g.
when setting the PID regulator, as it gives a view of
process reactions to reference changes. The display
readout is activated by pushing the [DISPLAY STA-
TUS] key.
Description of choice:
See parameter 009 Large display readout.
011 Small display readout 1.2
(DISPLAY LINE 1.2)
Value:
See parameter 009 Large display
readout
Motor cur-
rent [A][6]
Function:
See the functional description given under parameter
010 Small display readout.
Description of choice:
See parameter 009 Large display readout.
012 Small display readout 1.3
(DISPLAY LINE 1.3)
Value:
See parameter 009 Large display
readout
Feedback
[unit] [3]
Function:
See the functional description given under parameter
010 Small display readout.
Description of choice:
See parameter 009 Large display readout.
013 Local control
(LOC CTRL/CONFIG.)
Value:
Local not active (DISABLE) [0]
Local control and open loop without slip com-
pensation
(LOC CTRL/OPEN LOOP) [1]
Remote-operated control and open loop with-
out slip compensation
(LOC+DIG CTRL) [2]
Local control as parameter 100
(LOC CTRL/AS P100) [3]
Remote-operated control as parameter 100
(LOC+DIG CTRL/AS P100) [4]
Function:
This is where the required function is selected if, in
parameter 002 Local/remote operation, Local opera-
tion [1] has been chosen.
Description of choice:
If Local not active [0] is selected, it is not possible to
set a reference via parameter 003 Local reference.
In order to enable a shift to Local not active [0], param-
eter 002 Local/remote operation must be set to Remote
operation [0].
Local control and open loop [1] is used if the motor
speed is to be set via parameter 003 Local reference.
When this choice is made, parameter 100 Configura-
tion automatically shifts to Speed regulation, open
loop [0].
Remote-operated control and open loop [2] functions
in the same way as Local control and open loop [1];
VLT
®
2800 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.27.A2.22 - VLT
®
is a registered Danfoss trademark 37
Programming