however, the adjustable frequency drive can also be
controlled via the digital inputs.
For selections [1-2] control is shifted to open loop, no
slip compensation.
Local control as parameter 100 [3] is used when the
motor speed is to be set via parameter 003 Local ref-
erence, but
without parameter 100 Configuration auto-
matically shifting to Speed regulation, open loop [0].
Remote-operated control as parameter 100 [4] works
the same way as Local control as parameter 100 [3];
however, the adjustable frequency drive can also be
controlled via the digital inputs.
Shifting from Remote operation to Local operation in
parameter 002 Local/remote operation, while this pa-
rameter has been set to Remote-operated control and
open loop [1]: The present motor frequency and direc-
tion of rotation will be maintained. If the present direc-
tion of rotation does not respond to the reversing signal
(negative reference), the reference will be set to 0.
Shifting from Local operation to Remote operation in
parameter 002 Local/remote control, while this param-
eter has been set to Remote-operated control and open
loop [1]: The configuration selected in parameter 100
Configuration will be active. The shift will be smooth.
Shifting from Remote control to Local control in param-
eter 002 Local/remote operation, while this parameter
has been set to Remote-operated control as parameter
100 [4]: the present reference will be maintained. If the
reference signal is negative, the local reference will be
set to 0.
Shifting from Local operation to Remote operation in
parameter 002 Local/remote operation, while this pa-
rameter has been set to Remote operation: The local
reference will be replaced by the remote-operated ref-
erence signal.
014 Local stop
(LOCAL STOP)
Value:
Not active (DISABLE) [0]
Active (ENABLE) [1]
Function:
In this parameter, the local [STOP]-key can be engag-
ed or disengaged on the control panel and on the LCP
control panel.
Description of choice:
If Not active [0] is selected in this parameter, the
[STOP]-key will be inactive.
NOTE
If Not active [0] is selected, the motor can-
not be stopped by means of the [STOP]-
key.
015 Local jog
(LOCAL JOGGING)
Value:
Not active (DISABLE) [0]
Active (ENABLE) [1]
Function:
In this parameter, the jog function on the LCP control
panel can be engaged/disengaged.
Description of choice:
If Not active [0] is selected in this parameter, the [JOG]-
key will be inactive.
016 Local reverse
(LOCAL REVERSE)
Value:
Not active (DISABLE) [0]
Active (ENABLE) [1]
Function:
In this parameter you can select/deselect the reverse
function on the LCP control panel. The key can only
be used if parameter 002 Local/remote operation is set
to Local operation [1] and parameter 013 Localcon-
trol to Local control, open loop [1] or Local control as
parameter 100 [3].
VLT
®
2800 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
38 MG.27.A2.22 - VLT
®
is a registered Danfoss trademark

Table of Contents

Other manuals for Danfoss VLT 2800 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 2800 Series and is the answer not in the manual?

Danfoss VLT 2800 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT 2800 Series
CategoryDC Drives
LanguageEnglish

Related product manuals