The bus ter mination
68 = RxD/TxD-P∼ (red cable) 69 = RxD/TxD-N∼ (green cable)
It is essential that the bus line be terminated properly.
A m is match of impedance may result in reflections
onthelinethatwillcorruptdatatransmission.
- The PROFIBUS is provided with a suitable
termination which may b e activated by the switches
of the RS485 switch block located just above the
terminal block 67-70 (see drawing below). The
switches 1 and 2 should be on to terminate the b us.
- Most masters and repeaters are equipped
with their own termination.
- If an externa l termination circuit consisting of three
resistors is connec ted to the bus line a 5 V d.c.
power supply must be used, please note that this
must be galvanically isolated from the a.c. line.