FCM 300 / FCD 300 / VLT
®
2800 / DP V1 PROFIBUS
Physical connection FCD 300
The PROFIBUS is connected to the b us line
via, terminals 68 and 69.
It is recommended to use a master with a
galvanic isolated bus driver and with over voltage
protection (e.g. zenerdiode).
E
MC precautions
The following EMC precautions are recommended to
obtain interference free operation o f the PROFIBUS
network. Additional information on EMC can be found
in the design guide on the FCD 300 (MG.04.AX.02).
Please also consult the manual of the PROFIBUS
master for further installation guidelines.
Connection of the cable screen
The screen of the PROFIBUS cable must always be
connected to ground at both ends, that means the
screen must be co nnected to ground in all stations
connected to the PROFIBUS network. It is v ery
important to have a low impedance ground connection
of the screen, also a t high frequencies.This can be
obtained by connecting the surface of the screen to
ground, for example by means of a cable clamp.
The FCD 300 Series is provided with a spring loaded
clamp to enable a proper ground connection of the
PROFIBUS cable s creen. The scree n connection
is shown in the following drawing.
NB!:
Relevant national and local regulations,
for example regarding protective earth
connection, must be observed.
Cable connection FCD 300
The PROFIBUS communication cable must be kept
away from motor a nd brake resistor cab les to avoid
coupling of high frequency noise from one cable to
the other. Normally a distance of 200 mm is sufficient,
but it is generally recommended to keep the greatest
possible distance between the cables, especially whe re
cables are running in parallel over long distances.
If the PROFIBUS cable has to cross a motor and
braking resistance cable, i t should occur a t a 90° angle.
Earth connection FCD 300
It is important that all stations connected to the
PROFIBUS network are connected to the same
earth potential. The earth connection must have
a low HF (high freque n cy) impedance.
Especially when having long distances between the
stations in a P ROFIBUS network it can be necessary to
use additional potentia l equalizing cables, c onnecting
the individual stations to the same earth potential.
C
onnecting the bus line
MG.90.A5.02 - VLT is a registered Danfoss trademark
14

Other manuals for Danfoss VLT 2800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 2800 and is the answer not in the manual?

Danfoss VLT 2800 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 2800
CategoryDC Drives
LanguageEnglish

Related product manuals