Technical functions
600-605 Operating Data
Value:
Par. no. Description Display text Unit Range
600 Operating hours (OPERATING HOURS) Hours 0-130,000.0
601 Hours run (RUNNING HOURS) Hours 0-130,000.0
602 kWh counter (KWH COUNTER) kWh Depends on unit
603 Number of power-ups (POWER-UPS) Number of times 0-9999
604 Number of overtemperatures (OVERTEMPS) Number of times 0-9999
605 Number of overvoltages (OVERVOLTS) Number of times 0-9999
Function:
These parameters can be read out via the serial com-
munication port and the LCP control unit.
Description of choice:
Parameter 600, Operating hours:
Gives the number of hours the adjustable frequency
drive has been operating. The value is saved every
hour and when there is a line failure. This value cannot
be reset.
Parameter 601, Hours run:
Gives the number of hours the motor has been oper-
ating since the reset in parameter 619 Reset of hours
run counter. The value is saved every hour and when
there is a line failure.
Parameter 602, kWh counter:
Gives the adjustable frequency drive's output energy
in kWh. The calculation is based on the mean kW value
over one hour. This value can be reset using param-
eter 618 Reset of kWh counter.
Range: 0 - depends on unit.
Parameter 603, Number of power-ups:
Gives the number of power-ups of the supply voltage
undertaken on the adjustable frequency drive.
Parameter 604, Number of overtemperatures:
gives the number of overtemperature faults that have
been registered on the adjustable frequency drive's
heatsink.
Parameter 605, Number of overvoltages:
gives the number of overvoltages of the intermediate
circuit voltage in the adjustable frequency drive. This
is only counted when Alarm 7 Overvoltage is active.
NOTE
Parameters 615-617 Fault log cannot be
read out via the integral control unit.
615 Fault log: Error code
(F.LOG: ERROR COD)
Value:
[Index 1 - 10] Error code: 0 - 99
Function:
In this parameter it is possible to see the reason for a
trip (cut-out of the variable frequency drive) occurring.
10 [1-10] log values are defined.
The lowest log number [1] contains the latest/most re-
cently saved data value. The highest log number [10]
contains the oldest data value saved. If a trip occurs,
it is possible to see the cause, time and a possible val-
ue of the output current or output voltage.
Description of choice:
Given as a fault code, in which the number refers to a
table. See the table in Warnings/alarm messages.
616 Fault log: Time
(F. LOG: TIME)
Value:
[Index 1 - 10] Hours: 0 - 130,000.0
Function:
In this parameter, it is possible to see the total number
of operating hours in connection with the last 10 trips.
10 [1-10] log values are denoted. The lowest log num-
ber [1] contains the latest/most recently saved data
value, and the highest log number [10] contains the
oldest data value.
Description of choice:
Read out as one value.
VLT
®
2800 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.27.A2.22 - VLT
®
is a registered Danfoss trademark 93