Immunity In order to document immunity towards
interference from electrical phenomena
external, the following immunity test has
been made on a system consisting of a
VLT
®
frequency converter (with options, if
relevant), a screened control cable and
control box with potentiometer, screened
motor cable and motor.
Fault criteria and test were in accordance
with EN50082-2 and IEC 22G/21/CDV.
The tests were made using the following
standards:
IEC 1000-4-2 (IEC 801-2/1991):
Electrostatic discharges (ESD)
Simulation of electrostatic discharges from
human beings.
IEC 1000-4-3 (IEC 801-3):
Incoming electromagnetic field radia-
tion
Simulation of the effects of radar and radio
communication equipment as well as
mobile communications equipment.
IEC 1000-4-4 (IEC 801-4):
Burst transients
Simulation of interference brought about
by coupling with a contactor, relays or
similar devices.
IEC 1000-4-5:
Surge transients
Simulation of transients brought about e.g.
by lightening that strikes near installations.
ENV50141:
Cable-borne HF
Simulation of the effect of radio transmis-
sion equipment coupled to connection
cables.
VDE0160 class W2 test pulse:
Mains transients
Simulation of high-energy transients
brought about by main fuse breakage,
coupling with phase-compensation
batteries, etc.
VLT
®
3002-3008 380-500V, VLT
®
3002-3004 200V
Line 2kV/5kHz/DCN 2kV/2 4kV/12 - -
Motor 2kV/5kHz/CCC - - - -
Brake 2kV/5kHz/CCC - - - -
Control lines 2kV/5kHz/CCC - 2kV/2 * - -
PROFIBUS option 2kV/5kHz/CCC - - - -
Signal interface < 3 m 1kV/5kHz/CCC - - - -
Enclosure - - -
8 kV AD
6 kV CD
10V
Basic specification:
Acceptance criteria according to: IEC 22G/21/CDV, EN50082-2, 175R0740
N
Basic standard Burst
IEC 1000-4-4
Surge
IEC 1000-4-5
ESD
IEC 1000-4-2
Radiated
tromagn
.
IEC 1
0
Acceptance criterion B B B A
Port connection CM DM CM
Line OK OK OK - -
Motor OK - - - -
Brake OK - - - -
Control lines OK - OK - -
PROFIBUS option OK - - - -
Signal interface < 3 m OK - - - -
Enclosure - - - OK O
K
DM: Differential mode
CM: Common mode
CCC: Capacitive clamp coupling
DCN: Direct coupling network
* Injection on cable shield
** 2,3 x Û
N
: max. testpulse 1250 V peak
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 3022 and is the answer not in the manual?

Danfoss VLT 3022 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 3022
CategoryMedia Converter
LanguageEnglish

Related product manuals