153MG.30.A7.02 - VLT
®
is a registered Danfoss trademark
200/230 V
3002 3003 3004 3006 3008 3011 3016 3022 3032 3042 3052
Factory settings
Parameter
103 Motor power
0.75 1.5 2.2 4 5.5 7.5 11 15 22 30 37
104 Motor voltage
200 200 200 200 200 200 200 200 230 230 230
105 Motor frequency
50 50 50 50 50 50 50 50 60 60 60
107 Motor current
3.8 7.8 10.0 17.2 25.0 32.0 46.0 57.2 80.0 104.0 130.0
108
Motor magnetizing current 2.4 3.2 4.6 6.8 8.8 10.0 14.4 21.6 28.8 27.1 37.4
109 Start voltage
21.3 20.2 19.3 19.4 19.5 19.4 19.4 19.5 22.3 21.9 22.2
110 Start compensation
4.2 2.10 1.86 0.79 0.50 0.35 0.21 0.11 0.00 0.00 0.00
111 U/F ratio
3.75 3.70 3.80 3.80 3.80 3.80 3.80 3.80 3.70 3.65 3.70
112 Slip compensation
4.6 2.56 2.80 1.60 2.00 1.90 1.80 1.66 0.75 0.37 0.42
113 Negative slip comp.
4.6 2.56 2.80 1.60 2.00 1.90 1.80 1.66 0.75 0.37 0.42
202 Max frequency
50 50 50 50 50 50 50 50 60 60 60
209 Current limit
6.7 12.5 17.0 30.0 40.0 51.2 73.6 97.6 120.0 156.0 195.0
215 Ramp-up time
1 1 11010101010303030
216 Ramp-down time
1 1 11010101010303030
217 Alt. ramp-up time
1 1 11010101010303030
218 Alt. ramp-down time
1 1 11010101010303030
232 Current, min. value
1.2 1.6 2.3 3.4 4.4 5.0 7.2 10.8 14.4 13.6 18.7
308 D.C. brake voltage
22 16 21 17 14 11 10 10 0.0 0.0 0.0
311
Trip delay at inverter fault 22266666000
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com