EasyManuals Logo
Home>Danfoss>Media Converter>VLT 3022

Danfoss VLT 3022 User Manual

Danfoss VLT 3022
158 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #152 background imageLoading...
Page #152 background image
151MG.30.A7.02 - VLT
®
is a registered Danfoss trademark
Parameter
103 Motor power
0.75 1.5 2.2 4 5.5 7.5 11 15 22 30 37 45 55 75 90 110 132 160
104 Motor voltage
380 380 380 380 380 380 380 380 380 380 380 380 380 380 380 380 380 380
105 Motor frequency
50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
107 Motor current
2 3.7 5.3 9.1 12.2 15.8 22.8 31.1 42.8 59.3 72 86.2 106.3 134.1 166.8 197.8 230 272.4
108
Motor magnetizing current 1.1 2 2.4 3.6 4.6 5.4 8.6 10.2 13.1 20 20.3 28 34.5 40.1 53.6 60.3 67.8 77.5
109 Start voltage
40 39.1 36.8 35.6 35.4 35.2 35 34.9 34.9 36.8 36.2 36.8 36.7 36.7 36.7 36.7 36.7 36.7
110 Start compensation
16 5 5 2.3 1.6 1.19 0.7 0.46 0.28 0.21 0.23. 0000000
111 U/F ratio
6.84 6.94 7.03 7.13 7.13 7.18 7.2 7.28 7.3 7.32 7.22 7.33 7.31 7.3 7.3 7.3 7.3 7.3
112 Slip compensation
4.86 3.8 3.2 2.6 2.08 1.72 1.24 1.14 0.84 0.74 0.52 0.56 0.52 0.36 0.32 0.28 0.26 0.24
113 Negative slip comp.
4.86 3.8 3.2 2.6 2.08 1.72 1.24 1.14 0.84 0.74 0.52 0.56 0.52 0.36 0.32 0.28 0.26 0.24
202 Max. frequency
50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
209 Current limit
3.5 6.6 9 16 20.8 25.6 38.4 51.2 70.4 97.6 116.8 129 158 209 252 308 365 453
215 Ramp-up time
11111010101515151530303030303030
216 Ramp-down time
11111010101515151530303030303030
217 Alt. ramp-up time
11111010101515151530303030303030
218 Alt. ramp-down time
11111010101515151530303030303030
232 Current, min. value
0.6 1 1.2 1.8 2.3 2.7 4.3 5.1 6.6 10 10.2 14 17.3 20.1 26.8 30.2 33.9 38.8
308 D.C. brake voltage
28 25 28 21 14 13 11 12 11 21 20 20 0.0 0.0 0.0 0.0 0.0 0.0
311
Trip delay at inverter fault 2222999121212120000000
3002 3003 3004 3006 3008 3011 3016 3022 3032 3042 3052 3060 3075 3100 3125 3150 3200 3250
380/415 V
Factory settings
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 3022 and is the answer not in the manual?

Danfoss VLT 3022 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 3022
CategoryMedia Converter
LanguageEnglish