VLT
®
5000 Series
Technical
data
Braking at high overload torque level
Cycletime(s) Braking duty cycle at 100% torque Braking duty cycle at over
torque (150/160%)
200-240 V
5001-5027 120 Continuous 40%
5032-5052
300 10% 10%
380-500 V
5001-5102 120 Continuous 40%
5122-5252
600 Continuous 10%
5302
600 40% 10%
5352-5552
600 40%
1)
10%
2)
525-600 V
5001-5062 120 Continuous 40%
525-690 V
5042-5352 600 40% 10%
5402-5602
600 40%
3)
10%
4)
1) VLT 5502 at 90% torque. At 100% torque the braking duty cycle is 13%. At mains rating 441-500 V 100% torque the braking duty
cycle is 17%.
VLT 5552 at 80% torque. At 100% torque the braking duty cycle is 8%.
2) Based on 300 second cycle:
For VLT 5502 the torque is 145%.
For VLT 5552 the torque is 130%.
3) VLT 5502 at 80% torque.
VLT5602at71%torque.
4) Based on 300 second cycle.
For VLT 5502 the torque is 128%.
For VLT 5602 the torque is 114%.
Control card, digital inputs:
Number of programmable digital inputs ................................................................................................................ 8
Terminal nos. ............................................................................................................ 16, 17, 18, 19, 27, 29, 32, 33
Voltage level ........................................................................................................... 0-24 V DC (PNP positive logics)
Voltage level, logical 0 ............................................................................................................................ < 5 V DC
Voltage level, logical 1 ........................................................................................................................... >10 V DC
Maximum voltage on input ........................................................................................................................ 28 V DC
Input resistance, R
i
........................................................................................................................................ 2 k
Scanning time per input ............................................................................................................................. 3 msec.
Reliable galvanic isolation: All digital inputs are galvanically isolated from the supply voltage (PELV). In addition,
the digital inputs can be isolated from the other terminals on the control card by connecting an external 24
V DC supply and opening switch 4. VLT 5001-5062, 525-600 V do not meet PELV.
MG.51.A9.02 - VLT is a registered Danfoss trademark
11

Table of Contents

Other manuals for Danfoss VLT 5003

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5003 and is the answer not in the manual?

Danfoss VLT 5003 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 5003
CategoryDC Drives
LanguageEnglish

Related product manuals