VLT
®
5000 Series
Mechanical installation
Please pay attention to the requirements
that apply to integration and field mounting
kit, see the below list. The information given
in the list must be observed to avoid serious damage
or injury, especially when installing large units.
The frequency converter must be installed vertically.
The frequency converter is cooled by means of air
circulation. For the unit to be able to release its cooling
air, the minimum distance over and below the unit
must be as shown in the illustration below.
To protect the unit from overheating, it must be
ensured that the ambient temperature does not rise
above the max. temperature stated for the frequency
converter and that the 24-hour average temperature is
not exceeded . The max. temperature and 24-hour
average can be seen from the General Technical Data.
If the ambient temperature is in the range of 45°C -55°
C, derating of the frequency converter will become
relevant, see Derating for ambient temperature.
The service life of the frequency converter will
be reduced if derating for ambient temperature
is not taken into account.
MG.51.A9.02 - VLT is a registered Danfoss trademark
40

Table of Contents

Other manuals for Danfoss VLT 5003

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5003 and is the answer not in the manual?

Danfoss VLT 5003 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 5003
CategoryDC Drives
LanguageEnglish

Related product manuals