VLT 5000 Series protection:
Electronic motor thermal protection against overload.
Temperature monitoring of heat-sink ensures that the drive cuts out if the temperature reaches 90°C for
Chassis and Nema 1. For NEMA 12 cut-out temperature is 80°C. An overtemperature can only be reset when
the temperature of the heat-sink has fallen below 60°C.
For the units mentioned below, the limits are as follows:
- VLT 5122, 380-500 V, cuts out at 75°C and can be reset if the temperature has fallen below 60°C.
- VLT 5152, 380-500 V, cuts out at 80°C and can be reset if the temperature has fallen below 60°C.
- VLT 5202, 380-500 V, cuts out at 95°C and can be reset if the temperature has fallen below 65°C.
- VLT 5252, 380-500 V, cuts out at 95°C and can be reset if the temperature has fallen below 65°C.
- VLT 5302, 380-500 V, cuts out at 105°C and can be reset if the temperature has fallen below 75°C.
- VLT 5352-5552, 380-500 V, cut out at 85°C and can be reset if the temperature has fallen below 60°C.
- VLT 5042-5122, 525-690 V, cut out at 75°C and can be reset if the temperature has fallen below 60°C.
- VLT 5152, 525-690 V, cuts out at 80°C and can be reset if the temperature has fallen below 60°C.
- VLT 5202-5352, 525-690 V, cut out at 100°C and can be reset if the temperature has fallen below 70°C.
- VLT 5402-5602, 525-690 V, cut out at 75°C and can be reset if the temperature has fallen below 60°C.
The drive is protected against short-circuiting on motor terminals U, V, W.
The drive is protected against earth fault on motor terminals U, V, W.
Monitoring of the intermediate circuit voltage ensures that the drive cuts out if the intermediate circuit voltage
gets too high or too low.
If a motor phase is missing, the drive cuts out, see parameter 234 Motor phase monitor.
If there is a mains fault, the drive is able to carry out a controlled deramping.
If a mains phase is missing, the drive will cut out when a load is placed on the motor.
VLT
®
5000 Series
12 MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.

Table of Contents

Other manuals for Danfoss VLT 5027

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5027 and is the answer not in the manual?

Danfoss VLT 5027 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 5027
CategoryDC Drives
LanguageEnglish

Related product manuals