General technical data
AC line supply (L1, L2, L3):
Supply voltage 200-240 V units 3 x 200/208/220/230/240 V ±10%
Supply voltage 380-500 V units 3 x 380/400/415/440/460/500 V ±10%
Supply voltage 525-600 V units 3 x 525/550/575/600 V ±10%
Supply voltage 525-690 V units 3 x 525/550/575/600/690 V ±10%
Supply frequency 48-62 Hz +/- 1 %
See the section on special conditions in the Design Guide
Max. imbalance of supply voltage:
VLT 5001-5011, 380-500 V and 525-600 V and VLT 5001-5006, 200-240 V ±2.0% of rated supply voltage
VLT 5016-5062, 380-500 V and 525-600 V and VLT 5008-5027, 200-240 V ±1.5% of rated supply voltage
VLT 5072-5500, 380-500 V and VLT 5032-5052, 200-240 V ±3.0% of rated supply voltage
VLT 5075-5250, 525-600 V ±3.0% of rated supply voltage
True Power factor (Ȝ)
0.90 nominal at rated load
Displacement Power Factor (cos )
near unity (>0.98)
No. of switches on supply input L1, L2, L3 approx. 1 time/2 min.
Max. shortcircuit rating 100,000 A
VLT output data (U, V, W):
Output voltage 0-100% of supply voltage
Output frequency VLT 5001-5027, 200-240 V 0-132 Hz, 0-1000 Hz
Output frequency VLT 5032-5052, 200-240 V 0-132 Hz, 0-450 Hz
Output frequency VLT 5001-5052, 380-500 V 0-132 Hz, 0-1000 Hz
Output frequency VLT 5062-5302, 380-500 V 0-132 Hz, 0-450 Hz
Output frequency VLT 5352-5552, 380-500 V 0-132 Hz, 0-300 Hz
Output frequency VLT 5001-5011, 525-600 V 0-132 Hz, 0-700 Hz
Output frequency VLT 5016-5052, 525-600 V 0-132 Hz, 0-1000 Hz
Output frequency VLT 5062, 525-600 V 0-132 Hz, 0-450 Hz
Output frequency VLT 5042-5302, 525-690 V 0-132 Hz, 0-200 Hz
Output frequency VLT 5352-5602, 525-690 V 0-132 Hz, 0-150 Hz
Rated motor voltage, 200-240 V units 200/208/220/230/240 V
Rated motor voltage, 380-500 V units 380/400/415/440/460/480/500 V
Rated motor voltage, 525-600 V units 525/550/575 V
Rated motor voltage, 525-690 V units 525/550/575/690 V
Rated motor frequency 50/60 Hz
Switching on output Unlimited
Ramp times 0.05-3600 sec.
Torque characteristics:
Starting torque, VLT 5001-5027, 200-240 V and VLT 5001-5552, 380-500 V 160% for 1 min.
Starting torque, VLT 5032-5052, 200-240 V 150% for 1 min.
Starting torque, VLT 5001-5062, 525-600 V 160% for 1 min.
Starting torque, VLT 5042-5602, 525-690 V 160% for 1 min.
Starting torque 180% for 0.5 sec.
Acceleration torque 100%
Overload torque, VLT 5001-5027, 200-240 V and VLT 5001-5552, 380-500 V,
VLT 5001-5062, 525-600 V, and VLT 5042-5602, 525-690 V
160%
VLT
®
5000 Series
6 MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.

Table of Contents

Other manuals for Danfoss VLT 5027

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5027 and is the answer not in the manual?

Danfoss VLT 5027 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 5027
CategoryDC Drives
LanguageEnglish

Related product manuals