5 General Specifications
Mains supply (L1, L2, L3):
Supply voltage 380-500 V ±10%
Supply voltage 525-690 V ±10%
Mains voltage low/mains drop-out:
During low mains voltage or a mains drop-out, the frequency converters continues until the intermediate circuit voltage drops
below the minimum stop level, which corresponds typically to 15% below the drive's lowest rated supply voltage. Power-up and
full torque cannot be expected at mains voltage lower than 10% below the frequency converter’s lowest rated supply voltage.
Supply frequency 50/60 Hz ±5%
Max. imbalance temporary between mains phases 3.0 % of rated supply voltage
True Power Factor (λ) 0.9 nominal at rated load
Displacement Power Factor (cos ϕ) near unity (> 0.98)
Switching on input supply L1, L2, L3 (power-ups) maximum 1 time/2 min.
Environment according to EN60664-1 over-voltage category III/pollution degree 2
The unit is suitable for use on a circuit capable of delivering not more than 100.000 RMS symmetrical Amperes, 500/600/690 V
maximum.
Motor output (U, V, W)
Output voltage 0 - 100% of supply voltage
Output frequency 0 - 800* Hz
Switching on output Unlimited
Ramp times 0.01 - 3600 s
* Voltage and power dependent
Torque characteristics
Starting torque (constant torque) maximum 160% for 60 s
1)
once in 10 min.
Starting/overload torque (variable torque) maximum 110% up to 0.5 s
1)
once in 10 min.
Torque rise time in FLUX (for 5 kHz fsw) 1 ms
Torque rise time in VVC
plus
(independent of fsw) 10 ms
1)
Percentage relates to the nominal torque.
2)
The torque response time depends on application and load but as a general rule, the torque step from 0 to reference is 4-5 x
torque rise time.
Digital inputs
Programmable digital inputs 4 (6)
Terminal number 18, 19, 27
1)
, 29, 32, 33,
Logic PNP or NPN
Voltage level 0 - 24 V DC
Voltage level, logic'0' PNP < 5 V DC
Voltage level, logic'1' PNP > 10 V DC
Voltage level, logic '0' NPN
2)
> 19 V DC
Voltage level, logic '1' NPN
2)
< 14 V DC
Maximum voltage on input 28 V DC
Pulse frequency range 0 - 110 kHz
(Duty cycle) Min. pulse width 4.5 ms
Input resistance, R
i
approx.4
General Specifications
VLT
®
Automation Drive FC 300 Operating Instructions
90 MG33U402 - Rev. 2013-12-16
55

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 300 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 300 Series and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 300 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 300 Series
CategoryDC Drives
LanguageEnglish

Related product manuals