Dotted
line
Parameter 4-44 Motor Speed Monitor Max
Option
Name
Description
[0]
Disabled
[1]
Warning
The drive reports warning 101, Speed monitor when the speed is outside the limit.
[2]
Trip
The drive trips and reports alarm 101, Speed monitor.
[3]
Jog
[4]
Freeze output
[5]
Max speed
[6]
Switch to open loop
[7]
Select setup 1
[8]
Select setup 2
[9]
Select setup 3
[10]
Select setup 4
[11]
Stop & trip
[12]
Trip/warning
The drive reports alarm 101, Speed monitor in running mode and warning 101, Speed monitor in
stop or coast mode. This option is only available in closed-loop operation.
[13]
Trip/catch
Select when there is a need to catch a load, for example when mechanical braking fails. This op-
tion is available in closed loop only. The drive trips and reports alarm 101, Speed monitor in run-
ning mode. In stop mode, the drive catches the flying load and reports warning 101, Speed moni-
tor. In catch mode, the drive applies holding torque to control the 0 speed on a potentially mal-
functioning brake (closed loop). To exit this mode, send a new start signal to the drive. A coast or
Safe Torque Off also terminates the function.
Parameter 4-44 Motor Speed Monitor Max
Table 287: Parameter 4-44 Motor Speed Monitor Max
4-44 Motor Speed Monitor Max
Default value: 300 RPM
Parameter type: Range, 10 - 500 RPM
Setup: All setups
Conversion index: 67
Data type: Uint16
Change during operation: True
N O T I C E
Only available in flux control principle.
Enter the maximum allowable speed deviation between the actual mechanical shaft speed and the value in parameter 16-48 Speed
Ref. After Ramp [RPM].
Parameter 4-45 Motor Speed Monitor Timeout
Table 288: Parameter 4-45 Motor Speed Monitor Timeout
4-45 Motor Speed Monitor Timeout
Default value: 0.1 s
Parameter type: Range, 0 - 60 s
Setup: All setups
Conversion index: -2
Data type: Uint16
Change during operation: True
AU275636650261en-000101 / 130R0334 | 163Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT CANopen MCA 105

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT CANopen MCA 105 and is the answer not in the manual?

Danfoss VLT CANopen MCA 105 Specifications

General IconGeneral
BrandDanfoss
ModelVLT CANopen MCA 105
CategoryDC Drives
LanguageEnglish

Related product manuals