Option
Name
Description
[0]*
Off
C A U T I O N
RISK OF MOTOR DAMAGE
Using this option may lead to motor damage.
The drive does not issue a missing motor phase alarm.
[1]
On
Before each start, the drive checks if all 3 motor phases are present. The check is performed without any shaft
movement. The function also enables 3-phase detection in U/f and VVC+ mode. See description in parameter
4-58 Missing Motor Phase Function.
The table details the motor check at start for different motor control principles.
Table 301: Motor Check at Start for Different Motor Control Principles
Option
Motor Check
at Start
U/f
VVC
+
Flux
open
loop
Flux
closed
loop
[0]
Off
No function.
[1]
On
Check for missing motor phase before start is executed and enables
3-phase detection for U/f and VVC+ in parameter 4-58 Missing Motor
Phase Function.
5.5.6 4-6* Speed Bypass
Some systems require that certain output frequencies or speeds are avoided due to resonance problems in the system. A maximum
of 4 frequency or speed ranges can be avoided.
Parameter 4-60 Bypass Speed From [RPM]
Table 302: Parameter 4-60 Bypass Speed From [RPM]
4-60 Bypass Speed From [RPM]
Default value: Size related
Parameter type: Range, 0 - setting in par. 4-13 RPM, Array [4]
Setup: All setups
Conversion index: 67
Data type: Uint16
Change during operation: True
Some systems call for avoiding certain output speeds due to resonance problems in the system. Enter the lower limits of the speeds
to be avoided.
Parameter 4-61 Bypass Speed From [Hz]
Table 303: Parameter 4-61 Bypass Speed From [Hz]
4-61 Bypass Speed From [Hz]
Default value: Size related
Parameter type: Range, 0 - setting in par. 4-14 Hz, Array [4]
Setup: All setups
Conversion index: -1
Data type: Uint16
Change during operation: True
Some systems require that certain output frequencies or speeds are avoided due to resonance problems in the system. Enter the
lower limits of the speeds to be avoided.
Parameter 4-62 Bypass Speed To [RPM]
Table 304: Parameter 4-62 Bypass Speed To [RPM]
4-62 Bypass Speed To [RPM]
Default value: Size related
Parameter type: Range, 0 - setting in par. 4-13 RPM, Array [4]
Setup: All setups
Conversion index: 67
Data type: Uint16]
Change during operation: True
AU275636650261en-000101 / 130R0334168 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT CANopen MCA 105

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT CANopen MCA 105 and is the answer not in the manual?

Danfoss VLT CANopen MCA 105 Specifications

General IconGeneral
BrandDanfoss
ModelVLT CANopen MCA 105
CategoryDC Drives
LanguageEnglish

Related product manuals