Parameter 42-44 Deceleration Rate
Table 1392: Parameter 42-44 Deceleration Rate
42-44 Deceleration Rate
Default value: 1500/s
Parameter type: Range, 1 - 30000/s
Setup: All setups
Conversion index: 0
Data type: Uint16
Change during operation: False
Deceleration rate for the SS1 slope-based ramp type.
Parameter 42-45 Delta V
Table 1393: Parameter 42-45 Delta V
42-45 Delta V
Default value: 120 RPM
Parameter type: Range, 1 - 10000 RPM
Setup: All setups
Conversion index: 67
Data type: Uint16
Change during operation: False
Tolerance between calculated and actual speed that the safety option allows.
Parameter 42-46 Zero Speed
Table 1394: Parameter 42-46 Zero Speed
42-46 Zero Speed
Default value: 10 RPM
Parameter type: Range, 1 - 600 RPM
Setup: All setups
Conversion index: 67
Data type: Uint16
Change during operation: False
When this speed is reached, the safety option activates the STO.
Parameter 42-47 Ramp Time
Table 1395: Parameter 42-47 Ramp Time
42-47 Ramp Time
Default value: 1 s
Parameter type: Range, 0.1 - 3600 s
Setup: All setups
Conversion index: 0
Data type: Uint16
Change during operation: False
The time it takes to ramp down to 0 RPM.
Parameter 42-48 S-ramp Ratio at Decel. Start
Table 1396: Parameter 42-48 S-ramp Ratio at Decel. Start
42-48 S-ramp Ratio at Decel. Start
Default value: 50%
Parameter type: Range, 1 - 99%
Setup: All setups
Conversion index: 0
Data type: Uint8
Change during operation: False
The proportion of the total ramp-down time (parameter 42-42 Delay Time) where the deceleration torque increases. The larger the
percentage value, the greater the jerk compensation achieved, and thus the lower the torque jerks in the application.
Parameter 42-49 S-ramp Ratio at Decel. End
Table 1397: Parameter 42-49 S-ramp Ratio at Decel. End
42-49 S-ramp Ratio at Decel. End
Default value: 50%
Parameter type: Range, 1 - 99%
Setup: All setups
Conversion index: 0
Data type: Uint8
Change during operation: False
AU275636650261en-000101 / 130R0334674 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT CANopen MCA 105

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT CANopen MCA 105 and is the answer not in the manual?

Danfoss VLT CANopen MCA 105 Specifications

General IconGeneral
BrandDanfoss
ModelVLT CANopen MCA 105
CategoryDC Drives
LanguageEnglish

Related product manuals