Parameter 42-44 Deceleration Rate
Table 1392: Parameter 42-44 Deceleration Rate
Parameter type: Range, 1 - 30000/s
Change during operation: False
Deceleration rate for the SS1 slope-based ramp type.
Parameter 42-45 Delta V
Table 1393: Parameter 42-45 Delta V
Parameter type: Range, 1 - 10000 RPM
Change during operation: False
Tolerance between calculated and actual speed that the safety option allows.
Parameter 42-46 Zero Speed
Table 1394: Parameter 42-46 Zero Speed
Parameter type: Range, 1 - 600 RPM
Change during operation: False
When this speed is reached, the safety option activates the STO.
Parameter 42-47 Ramp Time
Table 1395: Parameter 42-47 Ramp Time
Parameter type: Range, 0.1 - 3600 s
Change during operation: False
The time it takes to ramp down to 0 RPM.
Parameter 42-48 S-ramp Ratio at Decel. Start
Table 1396: Parameter 42-48 S-ramp Ratio at Decel. Start
42-48 S-ramp Ratio at Decel. Start
Parameter type: Range, 1 - 99%
Change during operation: False
The proportion of the total ramp-down time (parameter 42-42 Delay Time) where the deceleration torque increases. The larger the
percentage value, the greater the jerk compensation achieved, and thus the lower the torque jerks in the application.
Parameter 42-49 S-ramp Ratio at Decel. End
Table 1397: Parameter 42-49 S-ramp Ratio at Decel. End
42-49 S-ramp Ratio at Decel. End
Parameter type: Range, 1 - 99%
Change during operation: False
AU275636650261en-000101 / 130R0334674 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide