3.8. Main Menu - Analog In/Out - Group 6
3.8.1. 6-** Analog In/Out
Parameter group for configuration of the analog input and output.
3.8.2. 6-0* Analog I/O Mode
Parameter group for setting up the analog I/O configuration.
The frequency converter is equipped with 2 analog inputs: Terminal 53 and 54. The analog inputs can freely be allocated to either voltage (0 - 10 V) or
current input (0/4 - 20 mA)
NB!
Thermistors may be connected to either an analog or a digital input.
6-00 Live Zero Timeout Time
Range: Function:
10s
*
[1 - 99 s]
Enter the Live Zero Time-out time period. Live Zero Time-out Time is active for analog inputs, i.e. terminal 53 or
terminal 54, allocated to current and used as reference or feedback sources. If the reference signal value asso-
ciated with the selected current input falls below 50% of the value set in par. 6-10, par. 6-12, par. 6-20 or par.
6-22 for a time period longer than the time set in par. 6-00, the function selected in par. 6-01 will be activated.
6-01 Live Zero Timeout Function
Option: Function:
Select the time-out function. The function set in par. 6-01 will be activated if the input signal on terminal 53 or
54 is below 50% of the value in par. 6-10, par. 6-12, par. 6-20 or par. 6-22 for a time period defined in par.
6-00. If several time-outs occur simultaneously, the frequency converter prioritises the time-out functions as
follows:
1. Par. 6-01
Live Zero Time-out Function
2. Par. 8-04
Control-word Time-out Function
The output frequency of the frequency converter can be:
[1] frozen at the present value
[2] overruled to stop
[3] overruled to jog speed
[4] overruled to max. speed
[5] overruled to stop with subsequent trip
If you select set-up 1-4, par. 0-10,
Active Set-up
, must be set to
Multi Set-up
, [9].
This parameter cannot be adjusted while the motor is running.
[0]
*
Off
[1] Freeze output
[2] Stop
[3] Jogging
[4] Max. speed
[5] Stop and trip
3. Parameter Description VLT
®
HVAC Drive Programming Guide
80
MG.11.C5.02 - VLT
®
is a registered Danfoss trademark
3

Other manuals for Danfoss VLT FC 100 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 100 Series and is the answer not in the manual?

Danfoss VLT FC 100 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 100 Series
CategoryDC Drives
LanguageEnglish

Related product manuals