20 mA at an output below 100% of the maximum signal value. If 20 mA is the desired output current at a value
between 0 - 100% of the ful-scale output, program the percentage value in the parameter, i.e. 50% = 20 mA.
If a current between 4 and 20 mA is desired at maximum output (100%), calculate the percentage value as
follows:
20
mA
/
desired maximum current
×100%
i
.
e
.10
mA
:
20
mA
10
mA
×100%=200%
6-63 Terminal X30/8 Output Bus Control
Range: Function:
0 %
*
[0 – 100 %]
Contains the value to apply to the output terminal, when it is configured as [Bus Controlled].
6-64 Terminal X30/8 Output Timeout Preset
Range: Function:
0 %
*
[0 – 100 %]
Contains the value to apply to the output terminal, when it is configured as [Bus Controlled Timeout] and timeout
is detected.
3.9. Main Menu - Communications and Options - Group 8
3.9.1. 8-** Comm. and Options
Parameter group for configuring communications and options.
3.9.2. 8-0* General Settings
General settings for communications and options.
8-01 Control Site
Option: Function:
The setting in this parameter overrides the settings in par. 8-50 to 8-56.
[0]
*
Digital and ctrl. word Control by using both digital input and control word.
[1] Digital only Control by using digital inputs only.
[2] Control word only Control by using control word only.
8-02 Control Word Source
Option: Function:
Select the source of the control word: one of two serial interfaces or four installed options. During initial power-
up, the frequency converter automatically sets this parameter to
Option A
[3] if it detects a valid fieldbus option
installed in slot A. If the option is removed, the frequency converter detects a change in the configuration, sets
par. 8-02 back to default setting
FC Port
, and the frequency converter then trips. If an option is installed after
initial power-up, the setting of par. 8-02 will not change but the frequency converter will trip and display: Alarm
67
Option Changed
.
[0] None
[1] FC Port
[2] FC USB
[3] Option A
[4] Option B
[5] Option C0
[6] Option C1
VLT
®
HVAC Drive Programming Guide 3. Parameter Description
MG.11.C5.02 - VLT
®
is a registered Danfoss trademark
89
3

Other manuals for Danfoss VLT FC 100 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 100 Series and is the answer not in the manual?

Danfoss VLT FC 100 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 100 Series
CategoryDC Drives
LanguageEnglish

Related product manuals