Bit 6, Ref from net:
Bit 6 = "0" means that the reference comes from inputs to the drive.
Bit 6 = "1" means that the reference comes from DeviceNet.
Bit 7, At reference:
Bit 7 = "0" means that the motor is running, but that the present speed is different from the preset
speed reference, i.e. the speed is being ramped up/down during start/stop.
Bit 7 = "1" means that the drive and reference speeds are equal.
Bit 8 - 15, State attribute:
(Instance 71 only)
Represents the state attribute of the drive, as
indicated in the table to the right:
Bit Num-
ber
Meaning
8 (Vendor specific)
9 Start up
10 Not ready
11 Ready
12 Enabled
13 Stopping
14 Fault stop
15 Faulted
For more detail of the actual output speed, see the section
Actual Output Speed under Instances
20/70 and 21/71
.
4. How to Control the Frequency Converter FC 100/ 200/ 300 DeviceNet
30
MG.33.D3.02 - VLT
®