6.2. Parameter List
Par.
No. #
Parameter description Default value Range Conversion
index
Data type
8-00 Enabled Options All [1] [0 - 7] - 5
8-01 Control Site Dig. & ctrl. word [0] [0 - 2] - 5
8-02 Control Word Source FC RS485 [0] [0 - 4] - 5
8-03 Control Word Timeout Time 1s 0.1-18000 -1 7
8-04 Control Word Timeout Function Off [0] [0 - 10] -1 5
8-05 End ofTimeout Function Hold set-up [0] [0 - 1] - 5
8-06 Reset Control Word Timeout Do not reset [0] [0 - 1] - 5
8-07 Diagnosis Trigger Disable [0] [0 - 3] - 5
8-10 Control Word Profile FC profile [0] [0 - x] - 5
8-50 Coasting Select Logic OR [3] [0 - 3] - 5
8-51 Quick Stop Select Logic OR [3] [0 - 3] - 5
8-52 DC Brake Select Logic OR [3] [0 - 3] - 5
8-53 Start Select Logic OR [3] [0 - 3] - 5
8-54 Reversing Select Logic OR [3] [0 - 3] - 5
8-55 Set-up Select Logic OR [3] [0 - 3] - 5
8-56 Preset Reference Select Logic OR [3] [0 - 3] - 5
8-90 Bus Jog 1 Speed 100 rpm 0 - par. 4-13 67 6
8-91 Bus Jog 2 Speed 200 rpm 0 par. 4-13 67 6
10-00 CAN Protocol DeviceNet [1] [0 - 1] - 5
10-01 Baud Rate Select 125 Kbps [20] [20 - 22] - 5
10-02 MAC ID 63 0 - 63 0 5
10-05 Readout Transmit Error Counter 0 0 - 255 0 5
10-06 Readout Receive Error Counter 0 0 - 255 0 6
10-07 Readout Bus Off Counter 0 0 - 1000 0
10-10 Process Data Type Selection [0]/[2] [0 - 3] 0 5
10-11 Process Data Config Write 0 list 0 5
10-12 Process Data Config Read 0 list 0 5
10-13 Warning Parameter 0 0 - FFFF 0 5
10-14 Net Reference Off [0] [0 - 1] - 5
10-15 Net Control Off [0] [0 - 1] - 5
10-20 COS Filter 1 0 0 - FFFF 0 6
10-21 COS Filter 2 0 0 - FFFF 0 6
10-22 COS Filter 3 0 0 - FFFF 0 6
10-23 COS Filter 4 0 0 - FFFF 0 6
10-30 Array Index 0 0 - 255 0 6
10-31 Store Data Values Off [0] [0 - 2] - 5
10-32 DeviceNet Revision - - - 6
10-33 Store Always Off [0] [0 - 1] - 5
16-90 Alarm Word 0 0 - FFFF 0 7
16-92 Warning Word 0 0 - FFFF 0 7
6. Parameters FC 100/ 200/ 300 DeviceNet
66
MG.33.D3.02 - VLT
®
is a registered Danfoss trademark
6

Other manuals for Danfoss VLT FC 100 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 100 Series and is the answer not in the manual?

Danfoss VLT FC 100 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 100 Series
CategoryDC Drives
LanguageEnglish

Related product manuals