Bit 02, DC brake:
Bit 02 = ’0’ leads to DC braking and stop. Braking current and duration are set in par. 2-01
DC
Brake Current
and 2-02
DC Braking Time
.
Bit 02 = ’1’ leads to ramping.
Bit 03, Coasting:
Bit 03 = ’0’ causes the frequency converter to immediately "let go" of the motor (the output
transistors are "shut off"), so that it coasts to a standstill.
Bit 03 = ’1’ enables the frequency converter to start the motor if the other starting conditions have
been fulfilled.
NB!
In par. 8-50
Coasting Select
a selection is made to define how Bit 03 gates with the
corresponding function on a digital input.
Bit 04, Quick stop:
Bit 04 = ’0’ causes a stop, in which the motor speed is ramped down to stop via par. 3-81
Quick
Stop Ramp Time
.
Bit 05, Hold output frequency:
Bit 05 = ’0’ causes the present output frequency (in Hz) to freeze. The frozen output frequency
can then be changed only by means of the digital inputs (parameters 5-10 to 5-15) programmed
to Speed up and Speed down.
NB!
If Hold output is active, only the following can stop the frequency converter:
Bit 03 Coasting stop
•Bit 02 DC braking
Digital input (parameters 5-10 to 5-15) programmed to DC braking, Coast-
ing stop or Reset and coasting stop.
Bit 06, Ramp stop/start:
Bit 06 = ’0’ causes a stop, in which the motor
speed is ramped down to stop via the selected
ramp down
parameter.
Bit 06 = ’1’ permits the frequency converter to
start the motor, if the other starting conditions
have been fulfilled.
NB!
In par. 8-53
Start Select
a selection is made to define how Bit 06 Ramp stop/start
gates with the corresponding function on a digital input.
Bit 07, Reset:
Bit 07 = ’0’ does not cause a reset.
Bit 07 = ’1’ causes the reset of a trip. Reset is activated on the leading edge of the signal, i.e.
when changing from logic ’0’ to logic ’1’.
Bit 08, Jog:
Bit 08 = ’1’ causes the output frequency to be determined by par. 3-19
Jog Speed
.
FC 100/ 200/ 300 DeviceNet 4. How to Control the Frequency Converter
MG.33.D3.02 - VLT
®
is a registered Danfoss trademark
33
4

Other manuals for Danfoss VLT FC 100 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 100 Series and is the answer not in the manual?

Danfoss VLT FC 100 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 100 Series
CategoryDC Drives
LanguageEnglish

Related product manuals