3.9. Additional Connections
3.9.1. Mechanical Brake Control
In hoisting/lowering applications, it is necessary to be able to control an electro-
mechanical brake:
Control the brake using any relay output or digital output (terminal 27 or 29).
Keep the output closed (voltage-free) as long as the adjustable frequency drive is unable
to ‘support’ the motor, such as when the load is too heavy, for example.
Select
Mechanical brake control
[32] in par. 5-4* for applications with an electro-me-
chanical brake.
The brake is released when the motor current exceeds the preset value found in par.
2-20.
The brake is engaged when the output frequency is less than the frequency found in par.
2-21 or 2-22, and only if the adjustable frequency drive carries out a stop command.
If the adjustable frequency drive is in alarm mode or in an overvoltage situation, the mechanical
brake immediately cuts in.
3. How to Install
VLT
®
Automation Drive FC 300
Instruction Manual High Power
72
MG.33.U1.22 - VLT
®
is a registered Danfoss trademark.
3

Table of Contents

Other manuals for Danfoss VLT FC 300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 300 and is the answer not in the manual?

Danfoss VLT FC 300 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 300
CategoryDC Drives
LanguageEnglish

Related product manuals